background image

Insulation process

Apply insulation for the pipes separately at liquid side and gas side.

•  For the insulation to the pipes at gas side, be sure to use the material with heat-resisting temperature 

  248 °F (120 °C) or higher.

•  To use the attached insulation pipe, apply the insulation to the pipe connecting section of the indoor unit     

  securely without gap.

REQUIREMENT

•  Apply the insulation to the pipe connecting section of the indoor unit securely up to the root without exposure of   

  the pipe. (The pipe exposed to the outside causes water leak.)

•  Wrap insulation with its slits facing up (ceiling side).

Wrap the pipe with the attached insulation 

without any gap between the indoor unit.

The seam must be faced upward 

(ceiling side).

Insulation pipe 

(accessory)

Banding band 

(locally 

procured)

Insulation 

of the pipe

Union

Flare nut

Indoor unit

8

 

Electrical connection

 

WARNING

   • 

Use the specified wires for wiring connect the terminals. Securely fix them to prevent external forces    

      applied to the terminals from affecting the terminals.

      Incomplete connection or fixation may cause a fire or other trouble.

   • 

Connect earth wire. (grounding work)

 

   Incomplete grounding cause an electric shock.

      Do not connect earth wires to gas pipes, water pipes, lightning conductor or telephone earth wires.

   • 

Appliance shall be installed in accordance with national wiring regulations.

 

Capacity shortage of power circuit or incomplete installation may cause an electric shock or a fire.

 

CAUTION

   •  For power supply specifications, follow the Installation Manual of outdoor unit.

   •  Do not connect 208/230V~60 Hz power to the terminal blocks (

A

B

) for control wiring. 

      Otherwise, the system will fail.

   •  Do not damage or scratch the conductive core and inner insulator of power and system interconnection wires   

      duringpeeling them.

   •  Perform the electric wiring so that it does not come to contact with the high-temperature part of the pipe. 

      The coating may melt resulting in an accident.

   •  Do not turn on the power of the indoor unit until vacuuming of the refrigerant pipes completes. 

 

System interconnection wires specifications

 System 

 interconnection   

 wires*

AWG16 or more

(H07RN-F or 60245 IEC 66)

Up to

229'7"

(70 m)

*Number of wire x wire size

Remote controller wiring

 Remote controller wiring, remote controller inter-unit

 wiring

 Wire size: AWG20 to AWG16

 Total wire length of remote controller wiring and remote

 controller inter-unit wiring = L + L1 + L2 + … Ln

 In case of wired type only

 Up to 1640' 5" (500 m)

 In case of wireless type

 included

 Up to 1312' 4" (400 m)

 Total wire length of remote controller inter-unit wiring = L1 + L2 + … Ln

 Up to 656' 2" (200 m)

 

CAUTION

The remote controller wire and system interconnection wires cannot be parallel to contact each other and cannot 

be stored in the same conduits. If doing so, a trouble may be caused on the control system due to noise or other 

factor.

Remote 

controller 

wiring

L

L1

L2

Ln

Indoor unit

Indoor unit

Indoor unit

Indoor unit

Remote 

controller 

Remote controller inter-unit wiring

(Max. 8 units)

– 18 –

EN

35-EN

36-EN

1128950138-00_S01_297x210_96p_S_p70_220212.indd   19

3/23/2022   8:10:27 AM

Summary of Contents for RAV-SM122BTP-UL

Page 1: ...ype RAV SM122BTP UL RAV SM182BTP UL RAV SM242BTP UL RAV SM302BTP UL RAV SM362BTP UL RAV SM422BTP UL RAV SM482BTP UL For commercial use Pour usage commercial Para uso comercial Installation Manual 1 English 1128950138 1128950138 00_S01_297x210_96p_S_p70_220212 indd 1 3 23 2022 8 10 08 AM ...

Page 2: ...ng to refrigerant handling and piping work on the air conditioners made by Toshiba Carrier Corporation or alternatively he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work The qualified installer who is allowed to work at heights has been trained in matters relating to working ...

Page 3: ...ry 2 or damage 3 to property if the product is handled improperly 1 Serious bodily harm indicates loss of eyesight injury burns electric shock bone fracture poisoning and other injuries which leave aftereffect and require hospitalization or long term treatment as an outpatient 2 Slight injury indicates injury burns electric shock and other injuries which do not require hospitalization or long term...

Page 4: ...heights using a stand of 19 7 50 cm or more or to remove the intake grille of the indoor unit to undertake work Wear protective gloves and safety work clothing during installation servicing and removal Do not touch the aluminium fin of the unit You may injure yourself if you do so If the fin must be touched for some reason first put on protective gloves and safety work clothing and then proceed Be...

Page 5: ...ing the air conditioner If the compressor is operated with the valve open and without refrigerant pipe the compressor sucks air and the refrigeration cycles is over pressurized which may cause an injury Tighten the flare nut with a torque wrench in the specified manner Over tightening tighten of the flare nut may cause a crack in the flare nut after a long period which may result in refrigerant le...

Page 6: ... circuit breaker outdoors install one which is designed to be used outdoors Electrical wiring 5 Under no circumstances the power wire must not be extended Connection trouble in the places where the wire is extended may give rise to smoking and or a fire Electrical wiring work shall be conducted according to law and regulation in the community and installation manual Failure to do so may result in ...

Page 7: ...f at least 0 1 3 mm The installation fuse all types can be used must be used for the power supply line of this conditioner CAUTION Explanations given to user Upon completion of the installation work tell the user where the circuit breaker is located If the user does not know where the circuit breaker is he or she will not be able to turn it off in the event that trouble has occurred in the air con...

Page 8: ...d Blocked filters may cause the air conditioner s performance to deteriorate condensation to form the plastic parts to be damaged and other such problems to result Locations near obstructions such as ventilation openings or lighting fixtures where the flow of the blown air will be disrupted a disruption of the air flow may cause the air conditioner s performance to deteriorate or the unit to shut ...

Page 9: ...olume Low air volume operation time 4 hours Installation space Unit in mm Reserve sufficient space required for installation or service work Air discharge Ceiling A B 1 0 25 1 0 25 Inspection opening Ceiling opening 3 9 100 or more or more 98 4 2500 or more 2 8 70 or more 10 8 275 Floor surface 0 2 5 or more Ceiling Air intake Inspection opening Ceiling opening 22 4 570 1 0 25 Air discharge 3 9 10...

Page 10: ...ces Installation of hanging bolt Use M10 hanging bolts 4 pcs locally procured Matching to the existing structure set pitch according to size in the unit external view as shown below New concrete slab Install the bolts with insert brackets or anchor bolts Steel flame structure Use existing angles or install new support angles Existing concrete slab Use a hole in anchors hole in plugs or a hole in b...

Page 11: ...r 2 Remove Electrical control box cover and Partition electrical cover Remove the screws 1 parts Remove the Electrical control box cover Electrical cover 1 hole Partition electrical cover Remove Remove Grommet Screws 3 Change part electrical cover 1 hole to 2 holes and attach Electrical control box cover Electrical cover 2 holes 4 Attach the Electrical control box cover to unit Attach the screws 4...

Page 12: ... where the pipe connects to the indoor unit with proper heat insulation Improper heat insulation will cause condensation to form The drain pipe must be sloping downward at an angle of 1 100 or more and do not run the pipe up and down arched shape or allow it to form traps Doing so may cause abnormal sounds Restrict the length of the traversing drain pipe to 65 6 20 m or less For a long pipe provid...

Page 13: ...llowing the method shown in the following figure Then while performing a cooling operation check that the water drains from the drain pipe connecting port transparent and that no water is leaking from the drain pipe When the electrical and wiring work has not been completed To ensure the power has been turned off Disconnect the float switch connector 3P red from the connector CN34 red on the print...

Page 14: ...om the surface of the indoor unit Insulation locally procured Insulation of the drain connecting section accessory Indoor unit Duct Insulation material locally procured Connect a duct to the outside of the flange Flange locally procured Aluminum tape locally procured Aluminum tape locally procured Under surface Air intake side Indoor unit Flange Air discharge side CAUTION Incomplete insulation of ...

Page 15: ...in WG High tap 0 2 in WG High tap 300 500 700 900 1100 1300 1500 1700 1900 RAV SM362BTP UL RAV SM422BTP UL RAV SM482BTP UL Standard air flow 1177 CFM 1 1 1 0 0 9 0 8 0 7 0 6 0 5 0 4 0 3 0 2 0 1 0 0 Air flow rate CFM 300 500 700 900 1100 1300 1500 1700 1900 2100 0 6 in WG Mid tap 0 2 in WG Mid tap 0 6 in WG Low tap 0 2 in WG Low tap Standard filter pressure loss 0 8 in WG High tap 0 6 in WG High ta...

Page 16: ... star mark is below 0 6 in WG high speed fan tap line which means the unit needs to be set to 0 6 in WG external static pressure with high speed fan tap Please follow the process described in application controls of this manual for set up external static pressure NOTE Supply air CFM will follow the solid line fan curve shown in the above graph if there is any change in the external static pressure...

Page 17: ...3 6 1359 4 9 3 235 4 10 0 254 1 1 27 3 9 100 3 9 100 1 1 27 1 5 37 5 1 5 37 5 3 9 100 3 9 100 3 9 100 3 9 100 3 9 100 3 9 100 3 9 100 3 9 100 3 9 100 3 9 100 3 9 100 3 9 100 3 9 100 26 0 659 4 9 3 235 2 10 0 254 1 1 27 3 9 100 3 9 100 1 1 27 3 4 87 5 3 4 87 5 3 9 100 3 9 100 3 9 100 3 9 100 3 9 100 26 6 675 37 8 960 9 3 235 2 10 0 254 1 1 27 3 9 100 3 9 100 1 1 27 1 5 37 5 1 5 37 5 3 9 100 3 9 100...

Page 18: ...double spanner Use the tightening torque levels as listed in the following table Unit ft lbs N m Outer dia of connecting pipe Tightening torque 1 4 6 4 mm 10 13 14 18 3 8 9 5 mm 24 31 33 42 1 2 12 7 mm 37 46 50 62 5 8 15 9 mm 50 60 68 82 Tightening torque of flare pipe connections Pressure of R410A is higher than that of R22 Approx 1 6 times Therefore using a torque wrench tighten the flare pipe c...

Page 19: ...ock or a fire CAUTION For power supply specifications follow the Installation Manual of outdoor unit Do not connect 208 230V 60 Hz power to the terminal blocks A B for control wiring Otherwise the system will fail Do not damage or scratch the conductive core and inner insulator of power and system interconnection wires duringpeeling them Perform the electric wiring so that it does not come to cont...

Page 20: ...res through the bushing of wire connection holes of the indoor unit Keep a margin Approx 3 9 100 mm on a wire to hang down the electrical control box at servicing or other purpose The low voltage circuit is provided for the remote controller Do not connect the high voltage circuit Before performing wiring work in the electrical control box remove the air filter and the cover of the box fixed with ...

Page 21: ...factor 5 Setting louver position Change the louver indication setting to match the indoor unit type 6 Setting timer operation mode Set whether or not the operation mode can be selected when setting the schedule timer 7 DN setting Advanced settings using DN code DN setting Perform the advanced settings for the air conditioner Carry out the setting operation while the indoor unit is stopped Turn off...

Page 22: ...e indoor unit or structure of the room the detection temperature of heating can be raised Also use a circulator or other device to circulate heat air near the ceiling Follow to the basic operation procedure 1 2 3 4 5 6 For the CODE No in Procedure 3 specify 06 For the SET DATA in Procedure 4 select the SET DATA of shift value of detection temperature to be set up from the following table Energy sa...

Page 23: ...to select 4 Monitor function on the Field setting menu screen then push the Set F2 button Push the button to select the code to check data 2 Refer to the Installation Manual supplied with the indoor unit or outdoor unit or service manual for details about the check code and data 3 Push the CANCEL button to return to the Field setting menu screen Indoor unit data CODE No Data name 01 Room temperatu...

Page 24: ... indoor addresses are set randomly For this reason change the setting to match line addresses with indoor addresses NOTE Procedure example 1 Procedure example Manual address setup procedure While the operation stops change the setup Stop the operation of the unit 1 Push the MENU button to display the menu screen Push and hold the MENU button and the button at the same time to display the Field set...

Page 25: ...ed Indoor UNIT No before setup change is displayed 7 After check of the changed contents Push the No F2 button to finish the setting operation Setting appears on the screen for a while then the screen returns to the Field setting menu screen Pushing the No F2 button displays the unit selection screen when the group control is used Push the CANCEL button on the unit selection screen to finish the s...

Page 26: ...ion of check code date time and unit 4 Monitor function Monitoring data of sensor temperature rotating speed of the compressor or other factor 5 Setting louver position Change the louver indication setting to match the indoor unit type 6 Setting timer operation mode Set whether or not the operation mode can be selected when setting the schedule timer 7 DN setting Advanced settings using DN code Wi...

Page 27: ...ar Following inspection must be carried out by a qualified installer or qualified service person Parts Inspection method Heat exchanger Access from inspection opening and remove the access panel Examine the heat exchanger if there is any clogging or damages Fan motor Access from inspection opening and check if any abnormal noise can be heard Fan Access from inspection opening and remove the access...

Page 28: ...d Auto reset E09 Duplicated header remote controllers Remote controller Remote controller address setting error Two remote controllers are set as header in the double remote controller control The header indoor unit stops raising alarm and follower indoor units continue to operate E10 CPU CPU communication error Indoor Indoor P C board Communication error between main MCU and motor microcomputer M...

Page 29: ...N80 Entire stop L31 SIM Phase sequence error etc Outdoor Power supply phase sequence outdoor unit P C board Abnormal phase sequence of the 3 phase power supply Operation continued thermost at OFF Wired remote controller display Wireless remote controller Sensor block display of receiving unit Main defective parts Judging device Parts to be checked error description Air conditioner status Indicatio...

Page 30: ...in multi air conditioners is 0 019 lbs ft 0 3 kg m Total amount of refrigerant lbs kg If there are 2 or more refrigerating systems in a single refrigerating device the amounts of refrigerant should be as charged in each independent device 2 When there is an effective opening with the adjacent room for ventilation of leaking refrigerant gas opening without a door or an opening 0 15 or larger than t...

Page 31: ...TANDARD 0000 STATIC 1 0001 STATIC 2 0002 STATIC 3 0003 STATIC 4 0004 STATIC 5 0005 STATIC 6 0006 Have you changed lighting time of filter sign If not fill check mark in NO CHANGE and fill check mark in ITEM if changed respectively For check method refer to APPLICABLE CONTROLS in this manual Filter sign lighting time CODE NO 01 NO CHANGE NONE 0000 150H 0001 2500H 0002 5000H 0003 10000H 0004 Filter ...

Page 32: ...144 9 Moo 5 Bangkadi Industrial Park Tivanon Road Tambol Bangkadi Amphur Muang Pathumthani 12000 Thailand 1128950138 1128950138 00_S01_297x210_96p_S_p70_220212 indd 96 3 23 2022 8 12 28 AM ...

Reviews: