– 24 –
No.
3
4
Item
Room temp.
control
Automatic
capacity control
(GA control)
Outline of specifications
1) Adjustment range: Remote controller setup temperature (°C)
Setup air volume operation
Setup data
Setup temp. correction
0
2
4
6
+0°C
+2°C
+4°C
+6°C
1) Based on the difference between Ta and Ts, the operation
frequency is instructed to the outdoor unit.
2) Cooling operation
Every 90 seconds, the room temperature difference
between temperature detected by Ta and Ts and the varied
room temperature value are calculated to obtain the
correction value of the frequency command and then the
present frequency command is corrected.
Ta (n) – Ts (n)
: Room temp. difference
n
: Counts of detection
Ta (n-1) – Ts (n) : Varied room temp. value
n – 1
: Counts of detection of 90 seconds before
3) Heating operation
Every 1 minute (60 sec.), the room temperature
difference between temperature detected by Ta and Ts
and the varied room temperature value are calculated to
obtain the correction value of the frequency command
and then the present frequency command is corrected.
Ts (n) – Ta (n)
: Room temp. difference
n
: Counts of detection
Ta (n) – Ta (n – 1) : Varied room temp. value
n – 1
: Counts of detection of 1 minute before
NOTE)
In case that Low volume is set, the maximum frequency is
restricted to approx. [SB].
Remarks
2) Using the Item code 06, the setup temperature in heating
operation can be corrected.
Shift of suction
temperature in heating
operation
COOL
18 to 29
HEAT
18 to 29
AUTO
18 to 29
Setup data
2
0
Wired type
Indoor formation
1-way Air Discharge Cassette Type
2-way Air Discharge Cassette Type
Concealed Duct Standard Type
High Wall Type
Under Ceiling Type
Floor Standing Concealed Type
Floor Standing Type