No.
10
11
Item
After-heat
elimination
Louver
control
Outline of specifications
When heating operation stops, in some cases, the indoor fan
operates with (L) for approx. 30 seconds.
1) During the first operation after power on, louver position is
controlled automatically according to operation mode
(COOL/HEAT).
Remarks
Louver angle: 0°
( full close )
Cooling
48
°
Heating
80
°
2) When louver position is controlled by remote controller, the
unit’s microcomputer memorizes the position for use in the next
operation.
∗
The memorized louver position is cleared when power is
turned off, and returns to the state of 1) above.
3) Louver position setting
• Louver position can be set within the range below.
COOL/DRY
HEAT/FAN
4) Swing setting
• Louver moves within the range beloW.
All operation modes
5) When air conditioner opration stops, louver closes
automatically.
It keeps its position in the event of an alarm.
6) Louver tilts upward automatically during preparation for heating.
Full close
0°
Alarm:
A code number (except
F08 and L31) appears
on the remote controller
and the indoor unit stops.
12
HA control
1) This control is connected to TV control or remote start/stop I/F,
etc, and start/stop are available by HA signal input from the
remote position.
2) This control outputs start/stop status to HA output terminal.
3) I/O specifications conform to JEMA regulations.
In the group operation,
use this control by
connecting to either
master or follower
indoor unit.
FILE NO. SVM-
12004
–
33
–
Summary of Contents for RAV-SM307KRTP-A
Page 14: ...RAV SM806KRT E TR FILE NO SVM 12004 14 ...
Page 112: ...TOSHIBA CARRIER CORPORATION ...