10-4. Function Selection Setup (Wired Remote Controller Only)
<Procedure>
Perform setting while the air conditioner stops.
1
Push
TEST
+
SET
+
CL
buttons simultaneously for 4 seconds or more.
The first displayed unit No. is the header indoor unit address in the group control.
In this time, fan and louver of the selected indoor unit operate.
ò
2
Every pushing
UNIT LOUVER
button (button at left side), the indoor unit No. in the group control is
displayed one after the other. In this time, fan and louver of the selected indoor unit only operate.
ò
3
Using the set temperature
TEMP.
buttons, specify the CODE No. (DN).
ò
4
Using the timer time
TIME
buttons, select the SET DATA.
ò
5
Push
SET
button. (OK if indication lights)
• To change the selected indoor unit, proceed to Procedure
2
.
• To change CODE No. to be set up, proceed to Procedure
3
.
ò
6
Pushing
TEST
button returns the status to the normal stop status.
1 2 3 4 5 6
END
<Operation procedure>
3
6
1
4
5
2
SET
TIME
TIMER SET
TEST
FILTER
RESET
TEMP.
CL
FAN
SAVE
SWING/FIX
VENT
MODE
ON / OFF
UNIT LOUVER
FILE NO. SVM-
12004
–
68
–