– 63 –
NO
NO
YES
NO
YES
YES
∗
For RAV-SM562AT-E, RAV-SM563AT-E,
RAV-SP404AT-E,
RAV-SP454AT-E,
replace control P.C. board.
Are connections of
cable/connector normal?
Are cablings of power and
current sensor normal?
Is not winding shorted?
(Is resistance between windings 0.6 to 1.2
Ω
?)
Is compressor normal?
Is not earthed?
Is not winding opened?
Compressor error
→
Replace
Compressor error
→
Replace
Compressor error
→
Replace
Check and correct circuit cables.
Check and correct circuit cabling
such as cabling to compressor.
Check IPDU P.C. board.
Defect
→
Replace
Check IPDU.
Defect
→
Replace
∗
For RAV-SM562AT-E, RAV-SM563AT-E, RAV-SP404AT-E, RAV-SP454AT-E
replace control P.C. board.
YES
YES
NO
NO
NO
YES
[P29 error]
[H03 error]