– 7 –
<Twin type>
Indoor unit 1
RAV-
SM562MUT-E
SM562MUT-E
Model
Indoor unit 2
RAV-
SM562MUT-E
SM562MUT-E
Outdoor unit
RAV-
SM1102AT-E
SM1103AT-E
Cooling capacity
(kW)
10.0
10.0
Heating capacity
(kW)
11.2
11.2
Indoor unit
Power supply
1 phase 230V (220 – 240V) 50Hz
Running current
(A)
14.96 – 16.32
14.96 – 16.32
Power consumption
(kW)
3.52
3.52
Cooling
Power factor
(%)
98
98
EER
2.84
2.84
Energy efficiency class
∗
C
C
Electrical
Energy rating
∗∗
—
—
characteristics
Running current
(A)
13.35 – 14.56
13.35 – 14.56
Power consumption
(kW)
3.14
3.14
Heating
Power factor
(%)
98
98
COP
3.57
3.57
Energy efficiency class
∗
B
B
Energy rating
∗∗
—
—
Fan
Turbo fan
Fan unit
Standard air flow
H/M/L
(m³/min.)
13.3 / 11.2 / 9.1
Motor
(W)
60
Sound pressure level
H/M/L
(dB•A)
43 / 39 / 34
Sound power level
H/M/L
(dB•A)
58 / 54 / 49
Outdoor unit
Power supply
1 phase 230V (220 – 240V) 50Hz
Standard length
(m)
7.5
Outer
Min. length
(m)
5.0
Max. total length
(m)
50
dimension
Height
Outdoor lower
(m)
30
difference
Outdoor higher
(m)
30
Fan
Propeller fan
Fan unit
Standard air flow volume
(m³/min.)
75
Motor
(W)
100
63
Gas side
Main
(mm)
15.9
Connecting
Sub
(mm)
12.7
pipe
Liquid side
Main
(mm)
9.5
Sub
(mm)
6.4
Sound pressure level
Cooling/Heating
(dB•A)
53 / 54
Sound power level
Cooling/Heating
(dB•A)
70 / 71
∗
: IEC standard,
∗∗
: AS standard