– 8 –
<Triple type>
Indoor unit 1
RAV-SM562MUT-E
Model
Indoor unit 2
RAV-SM562MUT-E
Indoor unit 3
RAV-SM562MUT-E
Outdoor unit
RAV-SM1603AT-E
Cooling capacity
(kW)
14.0
Heating capacity
(kW)
16.0
Indoor unit
Power supply
1 phase 230V (220 – 240V) 50Hz
Running current
(A)
23.88 – 21.89
Power consumption
(kW)
4.99
Cooling
Power factor
(%)
95
EER
2.81
Electrical
Energy efficiency class
∗
C
characteristics
Running current
(A)
22.44 – 20.57
Power consumption
(kW)
4.69
Heating
Power factor
(%)
95
COP
3.41
Energy efficiency class
∗
B
Fan
Turbo fan
Fan unit
Standard air flow
H/M/L
(m³/min.)
13.3 / 11.2 / 9.1
Motor
(W)
60
Sound pressure level
H/M/L
(dB•A)
43 / 39 / 34
Sound power level
H/M/L
(dB•A)
58 / 54 / 49
Outdoor unit
Power supply
1 phase 230V (220 – 240V) 50Hz
Standard length
(m)
7.5
Min. length
(m)
5.0
Outer dimension
Max. total length
(m)
50
Height
Outdoor lower
(m)
30
difference
Outdoor higher
(m)
30
Fan
Propeller fan
Fan unit
Standard air flow volume
(m³/min.)
103
Motor
(W)
100 + 100
Gas side
Main
(mm)
15.9
Connecting pipe
Sub
(mm)
12.7
Liquid side
Main
(mm)
9.5
Sub
(mm)
6.4
Sound pressure level
Cooling/Heating
(dB•A)
51 / 53
Sound power level
Cooling/Heating
(dB•A)
68 / 70
∗
: IEC standard