– 23 –
Slim Duct Type
Installation Manual
Procedure
3
Using temp. setup
/
buttons, specify
CODE No. [
].
Procedure
4
Using timer time
/
buttons, select
SET DATA [
].
Procedure
5
Push
button. When the display changes from
flashing to lit, the setup is completed.
• To change settings of another indoor unit,
repeat from Procedure
2
.
• To change other settings of the selected indoor
unit, repeat from Procedure
3
.
Use
button to clear the settings.
To make settings after
button was pushed,
repeat from Procedure
2
.
Procedure
6
When settings have been completed, push
button to determine the settings.
When
button is pushed, “SETTING” flashes
and then the display content disappears and the
air conditioner enters the normal stop mode.
(While “SETTING” is flashing, no operation of the
remote controller is accepted.)
Setup of external static
pressure
Be sure to set up a tap change based upon the
resistance (external static pressure) of the duct to
be connected.
To set up a tap change, follow to the basic
operation procedure (
1
→
2
→
3
→
4
→
5
→
6
).
• Specify [5d] to the item code in procedure
3
.
• For the setup data of procedure
4
, select a
setup data of the external static pressure to be
set up from the following table.
<Change on wired remote controller>
When wireless remote controller is used
Change the external static pressure setting with
the DIP switch on the receiver section P.C. board.
For details, refer to the manual of the wireless
remote controller kit. The settings can also be
changed with the switch on the indoor
microcomputer P.C. board.
* However, once the setting is changed, setting to
0001 or 0006 is possible but setting to 0000
requires a setting data change to 0000 using the
wired remote controller (separately sold) with
the normal switch setting (factory setting).
To restore the factory settings
To return the DIP switch settings to the factory
settings, set SW501-1 and SW501-2 to OFF,
connect a separately sold wired remote controller,
and then set the data of CODE No. [5d] to “
0000
”
in “Setup of external static pressure” on this page.
Setup data
External static pressure
0000
10 Pa
Standard (At shipment)
0001
20 Pa
High static pressure 1
0003
35 Pa
High static pressure 2
0006
50 Pa
High static pressure 3
Setup data
SW501-1
SW501-2
0000
(Factory shipping)
OFF
OFF
0001
ON
OFF
0003
OFF
ON
0006
ON
ON
SW501-1
MCU(IC501)
SW501-2
23-EN
+00EH99861401_01EN_SlimDuct_IM.book Page 23 Saturday, March 8, 2008 11:20 AM