– 25 –
Slim Duct Type
Installation Manual
Remote controller switch monitoring function
This function is available to call the service monitor mode from the remote controller during a test run to
acquire temperatures of sensors of the remote controller, indoor unit, and outdoor unit.
1. Push
and
buttons simultaneously for at least 4 seconds to call the service monitor mode.
The service monitor indicator lights up and the header indoor unit number is displayed first. CODE No.
is also displayed.
2. Pushing TEMP.
buttons, select the number of sensor, etc. (CODE No.) to be monitored. (See
the following table.)
3. Pushing
(left side of the button), select an indoor unit to be monitored. The sensor
temperatures of indoor units and their outdoor unit in the control group are displayed.
4. Push
button to return to the normal display.
1
3
4
2
Indoor unit data
CODE No.
Data name
01
Room temperature (remote controller)
02
Indoor unit intake air temperature (TA)
03
Indoor unit heat exchanger (coil)
temperature (TCJ)
04
Indoor unit heat exchanger (coil)
temperature (TC)
F3
Indoor unit fan cumulative operating
hours (x1 h)
Outdoor unit data
CODE No.
Data name
60
Outdoor unit heat exchanger (coil)
temperature (TE)
61
Outside air temperature (TO)
62
Compressor discharge temperature
(TD)
63
Compressor suction temperature (TS)
64
—
65
Heatsink temperature (THS)
6A
Operating current (x1/10)
F1
Compressor cumulative operating
hours (x100h)
25-EN
+00EH99861401_01EN_SlimDuct_IM.book Page 25 Saturday, March 8, 2008 11:20 AM