6
1-3. Combination Specifications of Indoor Units with Outdoor Units
4-way Air Discharge Cassette type
Concealed Duct type
Under Ceiling type
High wall type
RAV-SM560UT-E
RAV-SM800UT-E
RAV-SP1100UT-E
RAV-SM1400UT-E
RAV-SP560AT-E
RAV-SP800AT-E
RAV-SP1100AT-E
RAV-SP1400AT-E
Cooling
Heating
Cooling
Heating
Cooling
Heating
Cooling
Heating
5.30
5.60
7.10
8.00
10.00
11.20
12.50
14.00
(2.20-5.60)
(2.20-7.10)
(2.20-8.00) (2.20-10.00) (3.00-12.00) (3.00-13.00) (3.00-14.00) (3.00-16.50)
3.46
4.67
3.68
3.94
4.17
4.27
3.51
3.91
1 phase 230V (220-240V) 50Hz
7.17-6.57
5.62-5.15
8.95-8.21
9.42-8.63
11.24-10.31 12.28-11.25 16.51-15.14 16.60-15.22
1.53
1.20
1.93
2.03
2.40
2.62
3.56
3.58
97
97
98
98
97
97
98
98
32/29/27
34/31/28
39/36/33
42/38/34
Indoor Unit
Outdoor Unit
Standard capacity (Note 1)
(kW)
Energy consumption effect ratio
Power supply
Electrical
Running current
(A)
characteristics Power
(kW)
consumption
Power factor
(%)
Sound level
High/Mid./Low
Indoor unit
(Note 2)
(dB•A)
Indoor Unit
Outdoor Unit
Standard capacity (Note 1)
(kW)
Energy consumption effect ratio
Power supply
Electrical
Running current
(A)
characteristics Power
(kW)
consumption
Power factor
(%)
Sound level
High/Mid./Low
Indoor unit
(Note 2)
(dB•A)
RAV-SM561BT-E
RAV-SM801BT-E
RAV-SM1101BT-E
RAV-SM1401BT-E
RAV-SP560AT-E
RAV-SP800AT-E
RAV-SP1100AT-E
RAV-SP1400AT-E
Cooling
Heating
Cooling
Heating
Cooling
Heating
Cooling
Heating
5.00
5.60
7.10
8.00
10.00
11.20
12.50
14.00
(2.20-5.60)
(2.20-7.00)
(2.20-8.00) (2.20-10.00) (3.00-12.00) (3.00-13.00) (3.00-14.00) (3.00-16.50)
3.60
4.67
3.38
3.94
4.00
4.27
3.21
3.91
1 phase 230V (220-240V) 50Hz
6.51-5.97
7.26-6.66
9.74-8.93
9.74-8.93
11.72-10.74 11.72-10.74 18.09-16.58 16.70-15.31
1.39
1.55
2.10
2.10
2.50
2.50
3.90
3.60
97
97
98
98
97
97
98
98
40/37/33
40/37/34
42/39/36
44/41/38
Indoor Unit
Outdoor Unit
Standard capacity (Note 1)
(kW)
Energy consumption effect ratio
Power supply
Electrical
Running current
(A)
characteristics Power
(kW)
consumption
Power factor
(%)
Sound level
High/Mid./Low
Indoor unit
(Note 2)
(dB•A)
RAV-SM561CT-E
RAV-SM801CT-E
RAV-SM1101CT-E
RAV-SM1401CT-E
RAV-SP560AT-E
RAV-SP800AT-E
RAV-SP1100AT-E
RAV-SP1400AT-E
Cooling
Heating
Cooling
Heating
Cooling
Heating
Cooling
Heating
5.00
5.60
7.10
8.00
10.00
11.20
12.50
14.00
(2.20-5.60)
(2.20-7.00)
(2.20-8.00) (2.20-10.00) (3.00-12.00) (3.00-13.00) (3.00-14.00) (3.00-16.50)
3.55
3.73
3.38
3.64
4.17
4.48
3.21
3.73
1 phase 230V (220-240V) 50Hz
6.61-6.06
7.03-6.44
9.74-8.93
10.20-9.35 11.24-10.31 11.72-10.74 18.09-16.58 17.39-15.94
1.41
1.50
2.10
2.20
2.40
2.50
3.90
3.75
97
97
98
98
97
97
98
98
36/33/30
38/36/33
41/38/35
43/40/37
Indoor Unit
Outdoor Unit
Standard capacity (Note 1)
(kW)
Energy consumption effect ratio
Power supply
Electrical
Running current
(A)
characteristics Power
(kW)
consumption
Power factor
(%)
Sound level
High/Mid./Low
Indoor unit
(Note 2)
(dB•A)
RAV-SM560KRT-E
RAV-SM800KRT-E
RAV-SP560AT-E
RAV-SP800AT-E
Cooling
Heating
Cooling
Heating
Cooling
Heating
Cooling
Heating
5.00
5.60
6.90
8.00
(2.20-5.60)
(2.20-7.00)
(2.20-8.00)
(2.20-9.50)
3.60
3.61
2.88
3.33
1 phase 230V (220-240V) 50Hz
6.51-5.97
7.26-6.66
11.13-10.20 11.13-10.20
1.39
1.55
2.40
2.40
97
97
98
98
32/29/27
32/29/27
Note 1 : The cooling capacities and electrical characteristics are measured under the conditions specified by JIS B 8616 based
on the reference piping 7.5m.
Note 2 : The sound level is measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured in
the actual operating environment become larger than the indicated values due to the effects of external sound.
Note
: Rated conditions
Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB