61
[P03 error]/[1E error]
[H01 error]/[1F error]
Check parts. Defect
Replace
* Refer to Characteristics-4.
Is not abnormal overload?
Is power voltage normal?
Is not abnormal overload?
Is charged refrigerant amount normal?
Are characteristics of
TD sensor resistance value normal?
Is the circuit detected by
current sensor normal?
Is protective control such as
discharge temprelease control normal?
Are connections of
cable/connector normal?
Correct the cabling and
connection of connector.
Improve and delete the cause
Replace TD sensor.
Improve power line.
Improve and delete the cause.
Check and correct circuit cables.
Check CDB.
Defect
Replace
Check and correct the charged
refrigerant amount.
Check IPDU.
Defect
Replace
NO
NO
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
YES
YES