background image

– 9 –

5

 Refrigerant 

piping

Piping connections are inside the front panel of the 
unit and the front panel and pipe cover needs to be 
removed before piping and wiring connections are 
made.

Piping can enter the outdoor unit from the back, from 
the side or from the bottom as shown

Front panel

Pipe cover

Rear

Side

Bottom

1. Remove the front panel of the unit.
2. Remove the pipe cover.
3. Remove the appropriate knockout depending on the 

orientation of the piping.

The pipe cover is easily mounted by cutting off 
the slit at the lower part of the pipe cover.

Be sure to wear heavy work gloves while working.

4. Remove the burrs from the knockout opening and 

use the factory supplied protective edge guard 
material around the opening to protect the piping 
and the wiring.

5. Remove the flare nut from the service valve on 

outdoor unit. Insert the flare nut into the field piping, 
and flare the pipe.

  Bend the pipe approx. 90 degree with a pipe bender 

for side and rear piping.

6. When the piping connections are complete re-install 

the pipe cover.

Flaring

1. Cut the pipe with a pipe cutter.
  Be sure to remove burrs that may cause a gas 

leak.

2. Insert the supplied flare nut into the pipe, and then 

flare the pipe.

  As the flaring sizes of R410A differ from those of 

refrigerant R22, the flare tools newly manufactured 
for R410A are recommended.

However, the conventional tools 
can be used by adjusting the 
projection margin of the copper 
pipe.

B

 

Projection margin in 

fl

 aring : B (Unit : in (mm))

Rigid (Clutch type)

Outer diameter of 

copper pipe

R410A tool used

Conventional 

tool used

R410A

0.04” - 0.06”

(1.0 - 1.5)

3/8” (9.5)

0 - 0.02” (0 - 0.5)

5/8” (15.9)

 

Flaring diameter size : A (Unit : in (mm))

Outer diameter of copper pipe

+0

-0.02"(–0.4)

3/8” (9.5)

0.52” (13.2)

5/8” (15.9)

0.78” (19.7)

In case of 

fl

 aring for R410A with the 

conventional 

fl

 are tool, pull the tool out 

approx. 0.02” (0.5 mm) more than that for 
R22 to adjust it to the speci

fi

 ed 

fl

 are size. 

The copper pipe gauge is useful for 
adjusting the projection margin size.

A

■ 

Tightening of Flare 
Connections

1. Align the centers of the flare connections and fully 

tighten the flare nuts with your fingers.

Valve at liquid side

Cap

Loosened

Piping valve

Tightened

Flare nut

2. Use two wrenches to loosen or tighten the flare nut 

on the gas service valve as shown in the figure.

  Use only one wrench to loosen or tighten the flare 

not on the liquid service valve.

  The final tightening with a torque wrench should be 

to the specifications shown in table below.

Unit : ft•lbs (N•m)

Outer diameter of copper pipe

Tightening torque

3/8” (9.5 mm)

24 - 31 (33 - 42)

5/8” (15.9 mm)

50 - 60 (68 - 82)

Valve at gas side

Cap

Charge ori

fi

ce

Loosened

Cover

Piping valve

Flare nut

Tightened

• 

After the installation work, be sure to check for gas 
leaks of the pipe connections with nitrogen.

NO GOOD

Cover

Charge ori

fi

ce

NO GOOD

 CAUTION

1. Do not put the crescent wrench on the charge 

orifice or cover.

  The valve may be broken.
2. If applying excessive torque, the nut may break 

according to some installation conditions.

• 

Pressure of R410A is higher than that of R22 
(Approx. 1.6 times).
Therefore, using a torque wrench, tighten the flare 
pipe connecting sections that connect the indoor/
outdoor units at the specified tightening torque.
Incomplete connections may cause not only a gas 
leak, but also trouble with the refrigeration cycle.

Do not apply refrigerant oil to the flared 
surface.

17-EN

18-EN

1131601101 EN FR ES.indb   9

1131601101 EN FR ES.indb   9

4/8/2565 BE   10:14

4/8/2565 BE   10:14

Summary of Contents for RAV-SP242AT2P-UL

Page 1: ...door Unit Model name For commercial use Pour usage commercial Para uso comercial Heat Pump Model RAV SP242AT2P UL 1131601101 English Installation Manual 1 English 1131601101 EN FR ES indb 1 1131601101 EN FR ES indb 1 4 8 2565 BE 10 14 4 8 2565 BE 10 14 ...

Page 2: ...er uses R410A an environmentally friendly refrigerant Contents 1 Precautions for safety 3 2 Accessory parts 5 3 Installation of R410A refrigerant air conditioner 6 4 Installation conditions 6 5 Refrigerant piping 9 6 Vacuum 10 7 Electrical work 12 8 Grounding 13 9 Finishing 13 10 Test run 13 11 Annual maintenance 13 12 Functions to be implemented locally 14 13 Troubleshooting 16 14 Appendix 17 15 ...

Page 3: ...s a person who installs repairs maintains relocates and removes the air conditioners made by Manufacturer He or she has been trained to install repair maintain relocate and remove the air conditioners made by Manufacturer or alternatively he or she has been instructed in such operations by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge relat...

Page 4: ...autions in the literature and on tags stickers and labels attached to the equipment Follow all safety codes Wear safety glasses and work gloves Keep quenching cloth and fire extinguisher nearby when brazing Use care in handling rigging and setting bulky equipment Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit Consult local bui...

Page 5: ...t gas has leaked during the installation work ventilate the room immediately If the leaked refrigerant gas comes in contact with fire noxious gas may be generated After the installation work confirm that refrigerant gas does not leak If refrigerant gas leaks into the room and flows near a fire source such as a cooking range noxious gas may be generated Electrical work must be performed by a qualif...

Page 6: ...ause burst and injure CAUTION Do not climb onto or place objects on top of the outdoor unit You may fall or the objects may fall off of the outdoor unit and result in injury Wear heavy gloves during the installation work to avoid injury EQUIPMENT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation Do not bury more than 36 in 914 mm of refrigerant pipe ...

Page 7: ...ected to indoor outdoor unit Item RAV SP242AT2P UL 16 5 to 164 1 5 to 50 m Addition of refrigerant at the local site in unnecessary for refrigerant pipe lengths up to 98 5 30 m If the reftigerant pipe length exceeds 98 5 30 m Add refrigerant in the amount given in Charging additional refrigerant Caution during addition of refrigerant Charge the refrigerant accurately Overcharging may cause serious...

Page 8: ...n where the operating noise of the outdoor unit is transmitted When the outdoor unit is installed in an elevated position be sure to secure its feet A location in which drain water poses any problems When an outdoor unit is installed in a location that is always exposed to strong winds like a coast or on the high stories of a building one of the following is recommended Install the unit so that it...

Page 9: ...m or less 3 Place unit on stand Make sure it is level and fasten securely to the stand As shown in the figure below install the foundation and vibration proof rubber pads to directly support the bottom surface of the fixing leg that is in contact with the bottom plate of the outdoor unit When installing the foundation for an outdoor unit with downward piping consider the piping work GOOD GOOD NO G...

Page 10: ...g diameter size A Unit in mm Outer diameter of copper pipe A 0 0 02 0 4 3 8 9 5 0 52 13 2 5 8 15 9 0 78 19 7 In case of flaring for R410A with the conventional flare tool pull the tool out approx 0 02 0 5 mm more than that for R22 to adjust it to the specified flare size The copper pipe gauge is useful for adjusting the projection margin size A Tightening of Flare Connections 1 Align the centers o...

Page 11: ...ovides the power for the indoor unit as well as the communication signal between the outdoor and indoor unit System interconnection wire size must be AWG16 Breaker must have a capacity specified in the following table All wiring must comply with local electric codes and NEC National Electric Code or CEC Canadian Electric Code Model RAV SP242 Power supply 208 230 V 60 Hz MCA 17 A MOCP MAX Fuse CB 2...

Page 12: ...ion Method chart EVACUATE BREAK VACUUM WITH DRY NITROGEN WAIT EVACUATE BREAK VACUUM WITH DRY NITROGEN WAIT EVACUATE CHECK FOR TIGHT DRY SYSTEM IF IT HOLDS DEEP VACCUM RELEASE CHARGE INTO SYSTEM Final Tubing Check IMPORTANT Check to be certain factory tubing on both indoor and outdoor unit has not shifted during shipment Ensure tubes are not rubbing against each other or any sheet metal Pay close a...

Page 13: ...lowing table All wiring must comply with local electric codes and NEC National Electric Code or CEC Canadian Electric Code Model RAV SP242 Power supply 208 230 V 60 Hz MCA 17 A MOCP MAX Fuse CB 25 A Breaker 20 A System interconnection wires AWG16 Field power supply wire AWG12 MCA Minimum Circuit Amps MOCP Maximum Over Protection Device Amps Connect the system interconnection indoor to outdoor wire...

Page 14: ...d piping 10Test run Turn on the leakage breaker at least 12 hours before starting a test run to protect the compressor during startup To protect the compressor power is supplied from the 208 230 VAC input to the unit to preheat the compressor Check the following before starting a test run That all pipes are connected securely without leaks That the valve is open If the compressor is operated with ...

Page 15: ...4 Yellow D805 Green or or or or or OFF or Rapid flashing OFF or Rapid flashing OFF or Rapid flashing OFF or Rapid flashing OFF or Rapid flashing ON 12Functions to be implemented locally Handling existing pipe When using the existing pipe carefully check for the following Wall thickness within the specified range Scratches and dents Water oil dirt or dust in the pipe Flare looseness and leakage fro...

Page 16: ... least 5 seconds to return to the initial status and then repeat the setting steps Steps taken to recover the refrigerant 1 Operate the indoor unit in the fan mode 2 Check that the LED displays are placed in their initial status If not place them in the initial status 3 Hold down SW01 for at least 5 seconds and check that D804 flashes slowly Fig 1 4 Press SW01 once to set the LED displays D800 to ...

Page 17: ...ou can check whether the existing piping settings are enabled 1 Check that the LED displays are placed in their initial status If not place them in the initial status 2 Hold down SW01 for at least 5 seconds and check that D804 flashes slowly Fig 9 3 Press SW01 four times to set the LED displays D800 to D805 to the LED displays for existing piping settings shown below If the setting is enabled D802...

Page 18: ...ness R410A 0 03 0 8 0 04 1 0 3 When the outdoor unit was left with the pipes disconnected or the gas leaked from the pipes and the pipes were not repaired and refilled There is the possibility of rain water or air including moisture entering the pipe 4 When refrigerant cannot be recovered using a refrigerant recovery unit There is the possibility that a large quantity of dirty oil or moisture rema...

Page 19: ...o prevent the writing from rubbing off 3 Prevent emission of the contained fluorinated greenhouse gas Ensure that the fluorinated greenhouse gas is never vented to the atmosphere during installation service or disposal When any leakage of the contained fluorinated greenhouse gas is detected the leak shall be stopped and repaired as soon as possible 4 Only qualified service personnel are allowed to...

Page 20: ...4 9 Moo 5 Bangkadi Industrial Park Tivanon Road Tambol Bangkadi Amphur Muang Pathumthani 12000 Thailand 1131601101 1131601101 EN FR ES indb 2 1131601101 EN FR ES indb 2 4 8 2565 BE 10 14 4 8 2565 BE 10 14 ...

Reviews: