background image

– 11 –

■ 

Evacuation

 CAUTION

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment 
damage or improper operation.
Never use the system compressor as a vacuum 
pump.

Refrigerant tubes and indoor heat exchanger should 
be evacuated using the recommended deep vacuum 
method of 500 microns. The alternate triple evacuation 
method may be used if the procedure outlined below is 
followed. Always break a vacuum with dry nitrogen.

■ 

System Vacuum and Charge

Using Vacuum Pump

1. Completely tighten flare nuts A, B, C, D, connect 

manifold gage charge hose to a charge port of the 
low side service valve.

Service Valve

C

D

A

B

Outdoor Unit

Refrigerant

Low Side

Service Valve

High Side

Indoor Unit

2. Connect charge hose to vacuum pump.
3. Fully open the low side of manifold gage.

Manifold

Manifold Gage

High side valve

Charge hose

Vacuum pump

Low side valve

Charge hose

Low side valve

500 microns

4. Start vacuum pump.
5. Evacuate using either deep vacuum or triple 

evacuation method.

6. After evacuation is complete, fully close the low 

side of manifold gage and stop operation of vacuum 
pump.

Deep Vacuum Method

The deep vacuum method requires a vacuum pump 
capable of pulling a vacuum of 500 microns and a 
vacuum gage capable of accurately measuring this 
vacuum depth. The deep vacuum method is the most 
positive way of assuring a system is free of air and 
liquid water.

Deep Vacuum Graph

500

0

1000

1500

2000

2500

3000

3500

4000

4500

5000

1

2

3

4

5

6

7

MICRONS

LEAK IN

SYSTEM

VACUUM TIGHT

TOO WET

TIGHT DRY

SYSTEM

MINUTES

Triple Evacuation Method

The triple evacuation method should only be used 
when vacuum pump is only capable of pumping down 
to 28 in. of mercury vacuum and system does not 
contain any liquid water.
Refer to “Triple Evacuation Method chart” and proceed 
as follows:
1. Pump system down to 28 in. of mercury and allow 

pump to continue operating for an additional 15 
minutes.

2. Close service valves and shut off vacuum pump.
3. Connect a nitrogen cylinder and regulator to system 

and open until system pressure is 2 psig.

4. Close service valve and allow system to stand for 

1 hr. During this time, dry nitrogen will be able to 
diffuse throughout the system absorbing moisture.

5. Repeat this procedure as indicated in the chart. 

System will then be free of any cotaminants and 
water vapor.

Triple Evacuation Method chart

EVACUATE

BREAK VACUUM WITH DRY NITROGEN

WAIT

EVACUATE

BREAK VACUUM WITH DRY NITROGEN

WAIT

EVACUATE

CHECK FOR TIGHT, DRY SYSTEM

(IF IT HOLDS DEEP VACCUM)

RELEASE CHARGE INTO SYSTEM

■ 

Final Tubing Check

IMPORTANT:

Check to be certain factory tubing on both indoor and 
outdoor unit has not shifted during shipment. Ensure 
tubes are not rubbing against each other or any sheet 
metal. Pay close attention to feeder rubes, making 
sure wire ties on feeder tubes are secure and tight.

■ 

Pump down process

1. Turn off the Air Conditioner system.
2.  Connect the charge hose from the manifold valve to 

the service port of the packed valve at gas side.

3. Turn on the Air Conditioner system in cooling 

operation more than 10 minutes.

4. Check the operating pressure of the system should 

be normal value.

  (Ref. with product specification)
5. Release the valve rod cap of both service valves.
6. Use the Hexagon wrench to turning the valve rod of 

Liquid side fully close.

  (*Make sure no entering air into the system)
7. Continue operate Air Conditioner system until and 

the gauge of manifold dropped into the range of 
0.5 - 0 kgf/cm

2

8. Use the Hexagon wrench to turning the valve rod of 

Gas side fully close.

  And turn off the Air Conditioner system immediately 

thereafter.

9. Remove the gauge manifold from the service port of 

the packed valve.

10.  Securely tighten the valve rod cap to the both 

service valves.

 CAUTION

Should be check the compressor operating 
condition while pumping down process. It must 
not any abnormal sound, more vibration. It is 
abnormal condition appears and must turn off the 
Air Conditioner immediately.

Open service valves

Open or close the valve.

 

Liquid side

Open the valve with a

 0.16” (4 mm) 

hexagon wrench.

 

Gas side

Valve unit

Using a straight blade 
screwdriver, turn it 90° 
counter clockwise until 
the valve is fully open 
(against the stop).

Charge ori

fi

ce

Flare nut

Handle position

Fully closed

Fully opened

Stop pin

Main stopper

• 

While the valve is fully opened, after the screwdriver 
has reached the stopper, do not apply torque 
exceeding 4 ft•lbs (5 N•m). Applying excessive 
torque may damage the valve.

Valve handling precautions

• 

Open the valve stem until it reaches the stop.
It is unnecessary to apply further force.

• 

Securely tighten the cap with a torque wrench.

• 

Cap tightening torque

Valve size

Ø3/8” (9.5 mm)

24 - 31 ft•lbs (33 - 42 N•m)

Ø5/8” (15.9 mm)

15 - 18 ft•lbs (20 - 25 N•m)

Charge port

10 - 13 ft•lbs (14 - 18 N•m)

21-EN

22-EN

1131601101 EN FR ES.indb   11

1131601101 EN FR ES.indb   11

4/8/2565 BE   10:14

4/8/2565 BE   10:14

Summary of Contents for RAV-SP242AT2P-UL

Page 1: ...door Unit Model name For commercial use Pour usage commercial Para uso comercial Heat Pump Model RAV SP242AT2P UL 1131601101 English Installation Manual 1 English 1131601101 EN FR ES indb 1 1131601101 EN FR ES indb 1 4 8 2565 BE 10 14 4 8 2565 BE 10 14 ...

Page 2: ...er uses R410A an environmentally friendly refrigerant Contents 1 Precautions for safety 3 2 Accessory parts 5 3 Installation of R410A refrigerant air conditioner 6 4 Installation conditions 6 5 Refrigerant piping 9 6 Vacuum 10 7 Electrical work 12 8 Grounding 13 9 Finishing 13 10 Test run 13 11 Annual maintenance 13 12 Functions to be implemented locally 14 13 Troubleshooting 16 14 Appendix 17 15 ...

Page 3: ...s a person who installs repairs maintains relocates and removes the air conditioners made by Manufacturer He or she has been trained to install repair maintain relocate and remove the air conditioners made by Manufacturer or alternatively he or she has been instructed in such operations by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge relat...

Page 4: ...autions in the literature and on tags stickers and labels attached to the equipment Follow all safety codes Wear safety glasses and work gloves Keep quenching cloth and fire extinguisher nearby when brazing Use care in handling rigging and setting bulky equipment Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit Consult local bui...

Page 5: ...t gas has leaked during the installation work ventilate the room immediately If the leaked refrigerant gas comes in contact with fire noxious gas may be generated After the installation work confirm that refrigerant gas does not leak If refrigerant gas leaks into the room and flows near a fire source such as a cooking range noxious gas may be generated Electrical work must be performed by a qualif...

Page 6: ...ause burst and injure CAUTION Do not climb onto or place objects on top of the outdoor unit You may fall or the objects may fall off of the outdoor unit and result in injury Wear heavy gloves during the installation work to avoid injury EQUIPMENT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation Do not bury more than 36 in 914 mm of refrigerant pipe ...

Page 7: ...ected to indoor outdoor unit Item RAV SP242AT2P UL 16 5 to 164 1 5 to 50 m Addition of refrigerant at the local site in unnecessary for refrigerant pipe lengths up to 98 5 30 m If the reftigerant pipe length exceeds 98 5 30 m Add refrigerant in the amount given in Charging additional refrigerant Caution during addition of refrigerant Charge the refrigerant accurately Overcharging may cause serious...

Page 8: ...n where the operating noise of the outdoor unit is transmitted When the outdoor unit is installed in an elevated position be sure to secure its feet A location in which drain water poses any problems When an outdoor unit is installed in a location that is always exposed to strong winds like a coast or on the high stories of a building one of the following is recommended Install the unit so that it...

Page 9: ...m or less 3 Place unit on stand Make sure it is level and fasten securely to the stand As shown in the figure below install the foundation and vibration proof rubber pads to directly support the bottom surface of the fixing leg that is in contact with the bottom plate of the outdoor unit When installing the foundation for an outdoor unit with downward piping consider the piping work GOOD GOOD NO G...

Page 10: ...g diameter size A Unit in mm Outer diameter of copper pipe A 0 0 02 0 4 3 8 9 5 0 52 13 2 5 8 15 9 0 78 19 7 In case of flaring for R410A with the conventional flare tool pull the tool out approx 0 02 0 5 mm more than that for R22 to adjust it to the specified flare size The copper pipe gauge is useful for adjusting the projection margin size A Tightening of Flare Connections 1 Align the centers o...

Page 11: ...ovides the power for the indoor unit as well as the communication signal between the outdoor and indoor unit System interconnection wire size must be AWG16 Breaker must have a capacity specified in the following table All wiring must comply with local electric codes and NEC National Electric Code or CEC Canadian Electric Code Model RAV SP242 Power supply 208 230 V 60 Hz MCA 17 A MOCP MAX Fuse CB 2...

Page 12: ...ion Method chart EVACUATE BREAK VACUUM WITH DRY NITROGEN WAIT EVACUATE BREAK VACUUM WITH DRY NITROGEN WAIT EVACUATE CHECK FOR TIGHT DRY SYSTEM IF IT HOLDS DEEP VACCUM RELEASE CHARGE INTO SYSTEM Final Tubing Check IMPORTANT Check to be certain factory tubing on both indoor and outdoor unit has not shifted during shipment Ensure tubes are not rubbing against each other or any sheet metal Pay close a...

Page 13: ...lowing table All wiring must comply with local electric codes and NEC National Electric Code or CEC Canadian Electric Code Model RAV SP242 Power supply 208 230 V 60 Hz MCA 17 A MOCP MAX Fuse CB 25 A Breaker 20 A System interconnection wires AWG16 Field power supply wire AWG12 MCA Minimum Circuit Amps MOCP Maximum Over Protection Device Amps Connect the system interconnection indoor to outdoor wire...

Page 14: ...d piping 10Test run Turn on the leakage breaker at least 12 hours before starting a test run to protect the compressor during startup To protect the compressor power is supplied from the 208 230 VAC input to the unit to preheat the compressor Check the following before starting a test run That all pipes are connected securely without leaks That the valve is open If the compressor is operated with ...

Page 15: ...4 Yellow D805 Green or or or or or OFF or Rapid flashing OFF or Rapid flashing OFF or Rapid flashing OFF or Rapid flashing OFF or Rapid flashing ON 12Functions to be implemented locally Handling existing pipe When using the existing pipe carefully check for the following Wall thickness within the specified range Scratches and dents Water oil dirt or dust in the pipe Flare looseness and leakage fro...

Page 16: ... least 5 seconds to return to the initial status and then repeat the setting steps Steps taken to recover the refrigerant 1 Operate the indoor unit in the fan mode 2 Check that the LED displays are placed in their initial status If not place them in the initial status 3 Hold down SW01 for at least 5 seconds and check that D804 flashes slowly Fig 1 4 Press SW01 once to set the LED displays D800 to ...

Page 17: ...ou can check whether the existing piping settings are enabled 1 Check that the LED displays are placed in their initial status If not place them in the initial status 2 Hold down SW01 for at least 5 seconds and check that D804 flashes slowly Fig 9 3 Press SW01 four times to set the LED displays D800 to D805 to the LED displays for existing piping settings shown below If the setting is enabled D802...

Page 18: ...ness R410A 0 03 0 8 0 04 1 0 3 When the outdoor unit was left with the pipes disconnected or the gas leaked from the pipes and the pipes were not repaired and refilled There is the possibility of rain water or air including moisture entering the pipe 4 When refrigerant cannot be recovered using a refrigerant recovery unit There is the possibility that a large quantity of dirty oil or moisture rema...

Page 19: ...o prevent the writing from rubbing off 3 Prevent emission of the contained fluorinated greenhouse gas Ensure that the fluorinated greenhouse gas is never vented to the atmosphere during installation service or disposal When any leakage of the contained fluorinated greenhouse gas is detected the leak shall be stopped and repaired as soon as possible 4 Only qualified service personnel are allowed to...

Page 20: ...4 9 Moo 5 Bangkadi Industrial Park Tivanon Road Tambol Bangkadi Amphur Muang Pathumthani 12000 Thailand 1131601101 1131601101 EN FR ES indb 2 1131601101 EN FR ES indb 2 4 8 2565 BE 10 14 4 8 2565 BE 10 14 ...

Reviews: