– 12 –
7
Electrical
work
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in
personal injury or death.
•
The unit cabinet must have an uninterrupted or
unbroken ground to minimize personal injury if
an electrical fault should occur. The ground may
consist of electrical wire or metal conduit when
installed in accordance with existing electrical
codes.
•
The appliance shall be installed in accordance
with national wiring regulations.
•
Before performing service or maintenance, be
sure main power switch is turned OFF.
CAUTION
All wiring and connections must comply with NEC,
CEC, local codes.
UNIT DAMAGE HAZARD
Failure to follow this caution may result in
damage or improper operation.
•
Unit failure as a result of operation on improper
line voltage or excessive phase imbalance
constitutes abuse and may cause damage to
electrical components.
•
Wrong wiring may cause a burn-out of some
electrical parts.
•
Do not damage or scratch the conductive core or
inner insulator of the power and inter-connecting
wires when peeling them.
holes
Electrical control box
Field wiring
terminal
blocks
Valve mounting
bracket
Front
panel
Conduit
connection
holes
Front pipe cover
Piping knockout
■
Field wiring
The dashed lines show field wiring.
L
1
L
2
L
1
L
2
L
1
L
2
S
S
(Field power
supply)
(System
interconnection wires)
Input
power
208/230 V~,
60 Hz
circuit breaker
ground
Outdoor unit
Indoor unit
Remote
controller
•
System interconnection wire size must be AWG16.
•
Breaker must have a capacity speci
fi
ed in the
following table.
•
All wiring must comply with local electric codes and
NEC (National Electric Code) or CEC (Canadian
Electric Code).
Model RAV-
SP242
Power supply
208/230 V, 60 Hz
MCA
17 A
MOCP (MAX Fuse/CB)
25 A
Breaker
20 A
System interconnection wires
AWG16
Field power supply wire
AWG12
MCA = Minimum Circuit Amps
MOCP = Maximum Over Protection Device Amps.
•
Connect the system interconnection (indoor to
outdoor) wires to the identical terminal numbers on
the terminal block of each unit.
Incorrect connection may cause a failure.
1. With the front panel removed the electrical control
box is exposed at the top right corner of the unit.
2. Terminate the field wiring conduit (if used) at the
conduit connection holes provided.
3. Route the field power wires and the system
interconnection wires as shown on the following
pages. Terminate the wires at field wiring terminal
blocks located immediately below the electrical
control box.
L
1
L
2
S
L
1
L
2
System
interconncection
terminal block
Field power supply
terminal block
Ground screw
System
interconnection
wires
Banding band
Field power
supply wires
Ground screw
■
Wiring
1. Remove front panel and remove the front pipe
cover.
Remove the
4 screws.
Front pipe cover
2. Remove the wire cover from back of the front pipe
cover.
Cable cover
Wire cover
3. Pass the wires through the conduit connection
holes and attach the conduit connecters.
Conduit connector
4. Connect the wires to the terminal blocks and fix
the wires to the wiring guide with the 3 included
banding band.
Terminal block
Wire guide
Fix with the
2 banding band
Do not make the
wires slack in this
section.
EN
TH
ID
23-EN
24-EN
1131601101 EN FR ES.indb 12
1131601101 EN FR ES.indb 12
4/8/2565 BE 10:14
4/8/2565 BE 10:14