– 3
4
–
FILE NO. SVM-13047
6-6-5. Final Installation Checks
Do not apply the refrigerator oil to the flare surface.
Existing pipe: NO
∗
Use a new pipes.
Clean the pipes or use the new pipes.
Trial run
Is it possible to operate the existing air conditioner?
Was not largely discolored oil or
a large quantity of remains discharged?
(When the oil deteriorates, the color of the
oil changes to muddy and black color.)
∗
After the existing air conditioner operated in cooling mode
for approx. 30 minutes or longer*, recover the refrigerant.
∗
For cooling the pipes and recovering of oil
s
Refrigerant recovery: Pump down method
∗
Remove the existing air conditioner from the piping and
carry out flashing (nitrogen pressure 0.5 Mpa) to remove
the remains inside of the pipe.
Note]
In case of twin, also be sure to flash the
branching
pipe.
Connect the indoor/outdoor units to the existing pipe.
s
Use a flare nut attached to the main unit for the
indoor/outdoor
units.
(Do not use the flare nut of the existing pipe.)
s
Re-machine the flare machining size to size for R410A.
∗
(Airtight test), Vacuum dry, Refrigerant charge,
Gas leak check
In case that the gas pipe Ø19 mm is used for the
outdoor unit of SP80 (3 HP) or higher:
(Gas pipe size of our R410A model 3 is Ø15.9 mm)
→
Turn the existing pipe switch on the cycle control
P.C board of the outdoor unit to ON side.
At shipment from factory OFF
→
ON for existing pipe
(Refer to the table below.) (Be sure to set the contents
in the table below in order to restrict the refrigerating
cycle pressure of the equipment in the pipe standard.)
Existing pipe SW
Nitrogen gas pressure 0.5 Mpa
H
A
(If there is discharge of remains,
it is judged that there is a large quantity of remains.)
If you are in trouble of
pipe cleaning, please contact us.
Piping necessary to change the flare nut/
machining size due to pipe compression.
1) Flare nut width: H
2) Flare machining size: A
(mm)
36
Ø19.0
29
Ø15.9
26
27
24
Ø12.7
22
Ø9.5
17
Ø6.4
Same
as above
Copper pipe
outer dia.
For R22
For R410A
Same as above
(mm)
24.0
Ø19.0
19.7
Ø15.9
16.6
Ø12.7
13.2
Ø9.5
9.1
23.3
19.4
16.2
13.0
9.0
Ø6.4
Copper pipe
outer dia.
For R22
For R410A
Becomes large a little for R410A
3 HP
Switch
Bit 3 of SW802
→
ON
Is there no scratch or dent on the existing pipes?
YES
YES
NO
NO
SVM-12085_001-050.indd 35
SVM-12085_001-050.indd 35
12/06/12 11:06 AM
12/06/12 11:06 AM
Summary of Contents for RAV-SP564ATP-A
Page 17: ... 17 FILE NO SVM 13047 2 CONSTRUCTION VIEWS EXTERNAL VIEWS 2 1 RAV SP56 ATP ...
Page 18: ... 18 FILE NO SVM 13047 2 2 RAV SP80 ATP ...
Page 23: ... 23 FILE NO SVM 13047 1 4 WIRING DIAGRAM 4 1 RAV SP56 ATP ...
Page 24: ... 24 FILE NO SVM 13047 4 2 RAV SP80 ATP ...
Page 100: ... 100 FILE NO SVM 13047 1 11 1 RAV SP564ATP A 11 EXPLODED VIEWS AND PARTS LIST ...
Page 104: ... 104 FILE NO SVM 13047 11 2 RAV SP804ATP A ...
Page 109: ......