– 8
2
–
FILE NO. SVM-13047
No.
1
Part name
Common
procedure
Procedure
CAUTION
Never forget to put on the gloves at working
time, otherwise an injury will be caused by
the parts, etc.
1. Detachment
1) Stop operation of the air conditioner, and
turn off the main switch of the breaker for
air conditioner.
2) Remove the valve cover.
(ST1T Ø4 × 8L, 3 pcs.)
s
After removing screw, remove the valve
cover pulling it downward.
3) Remove wiring cover
(PT2T Ø4 × 10L, 1 pc.), and then remove
connecting cable.
4) Remove the upper cabinet.
(ST1T Ø4 × 8L, 5 pcs.)
s
After taking off screws, remove the
upper cabinet pulling it upward.
2. Attachment
1) Attach the waterproof cover.
CAUTION
Be sure to attach a waterproof cover.
If it is not attached, there is a possibility that
water enters inside of the outdoor unit.
2) Attach the upper cabinet.
(ST1T Ø4 × 8L, 5 pcs.)
s
Hook the rear side of the upper cabinet
to claw of the rear cabinet, and then put
it on the front cabinet.
3) Perform cabling of connecting cables, and
fix with cord clamp.
(BT2T Ø4 × 12L, 3 pcs.)
4) Attach the wiring cover.
(PT2T Ø4 × 10L, 1 pc.)
5) Attach the valve cover.
(ST1T Ø4 × 8L, 3 pcs.)
Remarks
Valve
cover
Wiring
cover
Upper cabinet
Water-proof
cover
Front cabinet
10. DETACHMENTS
10-1. RAV-SP56
*
ATP
*
SVM-12085_051-114.indd 83
SVM-12085_051-114.indd 83
12/06/12 11:15 AM
12/06/12 11:15 AM
Summary of Contents for RAV-SP564ATP-A
Page 17: ... 17 FILE NO SVM 13047 2 CONSTRUCTION VIEWS EXTERNAL VIEWS 2 1 RAV SP56 ATP ...
Page 18: ... 18 FILE NO SVM 13047 2 2 RAV SP80 ATP ...
Page 23: ... 23 FILE NO SVM 13047 1 4 WIRING DIAGRAM 4 1 RAV SP56 ATP ...
Page 24: ... 24 FILE NO SVM 13047 4 2 RAV SP80 ATP ...
Page 100: ... 100 FILE NO SVM 13047 1 11 1 RAV SP564ATP A 11 EXPLODED VIEWS AND PARTS LIST ...
Page 104: ... 104 FILE NO SVM 13047 11 2 RAV SP804ATP A ...
Page 109: ......