- 40 -
Installation Location
WARNING
Install the outdoor unit properly in a location that is
durable enough to support the weight of the outdoor
unit.
Insufficient durability may cause the outdoor unit to fall,
which may result in injury.
CAUTION
Do not install the outdoor unit in a location that is
subject to combustible gas leaks.
Accumulation of combustible gas around the outdoor unit
may cause a fire.
Install the outdoor unit in a location that meets the
following conditions after the customer’s consent is
obtained.
• A well-ventilated location free from obstacles near the
air inlets and air outlet
• A location that is not exposed to rain or direct sunlight
• A location that does not increase the operating noise
or vibration of the outdoor unit
• A location that does not produce any drainage
problems from discharged water
Do not install the outdoor unit in the following
locations.
• A location with a saline atmosphere (coastal area) or
one that is full of sulfide gas (hot-spring area) (Special
maintenance is required.)
• A location subject to oil, vapor, oily smoke, or
corrosive gases
• A location in which organic solvent is used
• Places where iron or other metal dust is present. If iron
or other metal dust adheres to or collects on the
interior of the air conditioner, it may spontaneously
combust and start a fire.
• A location where high-frequency equipment
(including inverter equipment, private power
generator, medical equipment, and communication
equipment) is used (Installation in such a location may
cause malfunction of the air conditioner, abnormal
control or problems due to noise from such
equipment.)
• A location in which the discharged air of the outdoor
unit blows against the window of a neighboring house
• A location where the operating noise of the outdoor
unit is transmitted
• When the outdoor unit is installed in an elevated
position, be sure to secure its feet.
• A location in which drain water poses any problems.
CAUTION
1.
Install the outdoor unit in a location where the
discharge air is not blocked.
2.
When an outdoor unit is installed in a location that is
always exposed to strong winds like a coast or on
the high stories of a building, secure normal fan
operation by using a duct or wind shield.
3.
When installing the outdoor unit in a location that is
constantly exposed to strong winds such as on the
upper stairs or rooftop of a building, apply the
windproofing measures referred to in the following
examples.
1)
Install the unit so that its discharge port faces
the wall of the building.
Keep a distance 500 mm or more between the
unit and wall surface.
500 mm
2)
Consider the wind direction during the
operational season of the air conditioner, and
install the unit so that the discharge port is set
at a right angle relative to the wind direction.
• When using an air conditioner under low outside
temperature conditions (Outside temp:-5 °C or
lower) in COOL mode, prepare a duct or wind
shield so that it is not affected by the wind.
Necessary Space for Installation
(Unit: mm)
Obstacle at rear side
Upper side is free
1.
Single unit installation
2.
Obstacles on both right and left sides.
3.
Serial installation of two or more units
Obstacle also above unit
Strong wind
Strong wind
<Example>
Wind shield
Wind shield
150
or
mo
re
200 or
mo
re
150 or
more
300 or
more
The height of the
obstacle should
be lower than the
height of the
outdoor unit.
150 or
more
300 or
more
300 or
more
300 or
more
The height of the obstacle should be
lower than the height of the outdoor unit.
200
o
r
more
150 or
more
500 or
more
EN-79
EN-80
Summary of Contents for RAV-SP804ATJP-E
Page 54: ... 53 EN 105 EN 106 MEMO ...
Page 55: ... 54 MEMO EN 107 EN 108 ...
Page 56: ...1114550101 ...