17
Model name
RDA-S
2401HA / D
037-ME
2401HA / D
055-ME
2401HA / D
075-ME
3001HA / D
037-ME
3001HA / D
055-ME
3001HA / D
075-ME
Cooling capacity (*1)
kW
66.3
67.2
67.9
82.1
84.0
84.0
Cooling capacity (*2)
kW
48.8
49.5
50.0
55.1
56.4
56.4
Heating capacity
kW
74.3
75.0
75.3
93.0
94.5
94.5
Electrical
characteristics
Power supply
Voltage
3 phase 4wire 50 / 60 Hz 400 V
Running
current
50 Hz
A
6.42
9.00
11.00
6.56
9.04
10.9
60 Hz
A
6.34
9.12
12.35
6.47
9.37
11.5
Power
consumption
50 Hz
kW
3.20
4.09
4.97
3.32
4.13
4.90
60 Hz
kW
3.61
5.07
7.08
3.70
5.25
6.49
Starting
current
50 Hz
A
67.0
100
132
67.0
100
132
60 Hz
A
59.0
83.0
109
59.0
83.0
109
Appearance
W: Silky shade (1Y 8.5 / 0.5)
Dimension
Height
mm
2300
Width
mm
1800
Depth
mm
820
Total weight
kg
410
430
440
410
430
440
Heat exchanger
Copper tubes, Aluminum plate fins
Soundproof / Heat-insulating material
Polyolefin form insulation
Fan unit
Fan
Multi blades centrifugal; Belt drive
Standard air flow (*3)
m
3
/h
10800
12600
13800
12600
15300
15300
Air flow
limit
Lower
m
3
/h
9000
9600
Upper
m
3
/h
18000
18600
External
static
pressure
50 Hz
Pa
256
406
475
130
154
292
60 Hz
424
654
768
276
354
542
Motor
W
3700
5500
7500
3700
5500
7500
Air Filter
none
Controller
Remote controller (Optional accessory)
Connecting
pipe
Gas side
mm
Ø 34.9
Liquid side
mm
Ø 19.1
Drain port
Outer dim.
mm
VP30A (Ø 38)
Inner dim.
mm
VP25A (Ø 32)
Sound pressure level (*4)
50 Hz
dB(A)
58.7
63.1
64.9
55.7
58.6
62.3
60 Hz
dB(A)
62.4
66.7
68.5
60.4
63.6
66.5
(*1): Rated conditions
Cooling: Indoor 27 degC Dry Bulb / 19 degC Wet Bulb, Outdoor 35 degC Dry Bulb.
Heating: Indoor 20 degC Dry Bulb, Outdoor 7 degC Dry Bulb / 6 degC Wet Bulb.
Based on equivalent piping length of 7.5 m and piping height difference of 0 m.
(*2): Rated conditions
Cooling: Indoor 27 degC Dry Bulb / 19 degC Wet Bulb, Outdoor 46 degC Dry Bulb.
Based on equivalent piping length of 7.5 m and piping height difference of 0 m.
(*3): As air volume is fixed, by remote controller, air volume cannot be changed. When required high static pressure and
air volume change, a pulley change is requested.
(*4): The sound levels are measured in an anechoic chamber. Normally, the sound level measured in the actual operating
environment become bigger than the rated figures due to the effects of external sound.