152
RemotEye 4 User Manual – 90988-007
A.5
MODBUS (1X) INPUT REGISTERS FOR SINGLE PHASE UPS: ALARMS AND STATUS
All 1X registers are:
Data Type
– Discrete
Size
– 1-Bit
Access
– Read Only
Units
– True (1)/False (0)
Note 1:
The Modbus registers table style addressing is protocol base 0. If monitoring software uses PLC style addressing base 1, add one to the register number. For
example, Modbus address 30001 becomes PLC address 30002 ; address 10001 becomes PLC address 10002.
Note 2:
Please make sure the latest RemotEye 4 firmware revision is installed in order to use the Modbus register table below. If not, there will be inconsistencies
between RemotEye 4 internal register addressing and this manual. Go to www.toshibaups.com to get the latest RemotEye 4 firmware.
MODBUS (1X) INPUT REGISTER – SINGLE PHASE PLATFORMS
Registers
Description
1600XP(i)
T1000
T1000 (1-3kVA)
CMD
CMD
CMD
RMTI
-4
Statu
s
10001
RemotEye 4 Data Link
Y
Y
Y
10002
RemotEye 4 Network Link
Y
Y
Y
…
Reserved
N/A
N/A
N/A
….
Reserved
N/A
N/A
N/A
…..
Reserved
N/A
N/A
N/A
10020
Reserved
N/A
N/A
N/A
UPS M
ode
10021
Startup Mode
Y
Y
N/A
10022
Online Mode
Y
Y
Y
10023
Backup Mode
Y
Y
Y
10024
Bypass Mode
Y
Y
Y
10025
Shutdown Mode
Y
Y
Y
10026
Battery Test Mode
Y
Y
Y
10027
Pre-Charge Mode
N/A
N/A
N/A
10028
Gate-Check Mode
N/A
N/A
N/A
10029
Standby Mode
N/A
N/A
N/A
10030
Power Conditioner
N/A
N/A
N/A
10031
Start Inverter
N/A
N/A
N/A
10032
Stop Inverter
N/A
N/A
N/A
Summary of Contents for RemotEye 4
Page 1: ...RemotEye 4 User Manual Document Number 90988 007 September 2018 ...
Page 4: ...4 RemotEye 4 User Manual 90988 007 This Page Intentionally Left Blank ...
Page 12: ...12 RemotEye 4 User Manual 90988 007 This Page Intentionally Left Blank ...
Page 28: ...28 RemotEye 4 User Manual 90988 007 Figure 3 6 RemotEye 4 in 5000 Series 30kVA ...
Page 97: ...RemotEye 4 User Manual 90988 007 97 Figure 11 10 VM Remote Shutdown Test ...
Page 221: ...RemotEye 4 User Manual 90988 007 221 ...
Page 261: ......