166
RemotEye 4 User Manual – 90988-007
1600XP/XPi BACnet Analog Input Point Mapping
Inst.
ID
Object Name & Description
Units
Comments
92
Battery cabinet 2 Charger Voltage
Volts
93
Battery Cabinet 2 Ambient Temperature
°C
94
Battery Cabinet 2 Ambient Temperature
°F
Convert Celcius to Fahrenheit
EMD
95
Temperature in Celsius
°C
Note: "-1" means disabled or not connected
96
Temperature Fahrenheit
°F
Note: "-1" means disabled or not connected
97
Humidity
%
Note: "-1" means disabled or not connected
UPS
Hist
or
y Summ
ary
98
UPS History System Operation Time
DHM
RE3 Convert Seconds -> Days/Hours/Minutes
99
UPS History Inverter Operation Time
DHM
RE3 Convert Seconds -> Days/Hours/Minutes
100
UPS History Backup Operation Time
Seconds
101
UPS Lifetime Remaining
Months
102
UPS History Highest System Temperature
°C
103
UPS History Highest System Temperature
°F
Convert Celcius to Fahrenheit
104
UPS History Highest Battery Temperature
°C
105
UPS History Highest Battery Temperature
°F
Convert Celcius to Fahrenheit
106
UPS History Total Number Input Under Voltage
Times
107
UPS History Total Number Overloads
Times
108
UPS History Total Number Tests
Times
109
UPS History Total Number Backup
Times
110
UPS History Total Number Faults
Times
111
UPS History Total Number Operation Mode Change
Times
112
UPS History Total Number Warnings
Times
113
UPS History Total Number System Settings Changed
Times
114
UPS History Total Number Resets
Times
Summary of Contents for RemotEye 4
Page 1: ...RemotEye 4 User Manual Document Number 90988 007 September 2018 ...
Page 4: ...4 RemotEye 4 User Manual 90988 007 This Page Intentionally Left Blank ...
Page 12: ...12 RemotEye 4 User Manual 90988 007 This Page Intentionally Left Blank ...
Page 28: ...28 RemotEye 4 User Manual 90988 007 Figure 3 6 RemotEye 4 in 5000 Series 30kVA ...
Page 97: ...RemotEye 4 User Manual 90988 007 97 Figure 11 10 VM Remote Shutdown Test ...
Page 221: ...RemotEye 4 User Manual 90988 007 221 ...
Page 261: ......