RemotEye 4 User Manual – 90988-007
211
5000 (3P1) BACnet Analog Point Mapping
Instance ID
Object Name & Description
Units
Comments
Outp
ut P
aram
eter
s
24
Output Voltage
1 Volts
25
Output Rated Voltage
1 Volts
26
Output Voltage Percent
1%
27
Output Rated Voltage
1 Volts
28
Output Current
1 Amp
29
Output Current Percent
%
30
Output Load Percent
%
31
Ouput Rated Current
1 Amp
32
Output Frequency
0.01Hz
33
Output Rated Frequency
0.01Hz
34
Ouput Apparent Power
VA
35
Output Apparent Power Total %
X 1
36
Output Rated Apparent Power
KVA
Byp
ass
Par
ame
ter
s
37
Bypass Voltage
1 Volts
38
Bypass Voltage Percent
%
39
Bypass Rated Voltage
1 Volts
40
Bypass Current
1 Amps
41
Bypass Current %
%
42
Bypass Rated Current
1 Amp
43
Bypass Frequency
0.01Hz
44
Bypass Rated Frequency
0.01 Hz
DC
Bu
s
Par
ame
ter
s
45
DC bus Total Voltage
Vdc
Batte
ry Par
am
eter
s
46
Batteriy Installed Date
Strings
47
Elapsed Time on Battery Power
Seconds
48
Battery Voltage
Vdc
49
Battery Capacity
%
50
Battery Current
Adc
51
Battery Rated Voltage
1 Volts
Summary of Contents for RemotEye 4
Page 1: ...RemotEye 4 User Manual Document Number 90988 007 September 2018 ...
Page 4: ...4 RemotEye 4 User Manual 90988 007 This Page Intentionally Left Blank ...
Page 12: ...12 RemotEye 4 User Manual 90988 007 This Page Intentionally Left Blank ...
Page 28: ...28 RemotEye 4 User Manual 90988 007 Figure 3 6 RemotEye 4 in 5000 Series 30kVA ...
Page 97: ...RemotEye 4 User Manual 90988 007 97 Figure 11 10 VM Remote Shutdown Test ...
Page 221: ...RemotEye 4 User Manual 90988 007 221 ...