34
RemotEye 4 User Manual – 90988-007
Figure 4-3 Tera Term Opening Screen
4.
Click on each drop-down box as necessary to
adjust the serial port settings.
5.
Set the COM port parameters for:
Port:
(COM port for SPEAr)
Baud rate:
9600
Data:
8 Bit
Parity:
none
Stop:
1 bit
Flow control:
none
Transmit Delay:
0
6.
Click on the “OK” button.
7.
Set the RemotEye 4 IP Address for the target
network. See Section 4.2.3 Set the IP
Address.
4.2.4
Set the IP Address
1.
Install the Driver
2.
Connect the USB to mini-USB adapter cable provided in the RemotEye 4 package.
3.
Load and start a hyperterminal (Tera Term)
4.
Look for the SPEAr COM Port number.
5.
Click OK
6.
Set the COM port for SPEAr to the following settings:
Baud
9600 baud
Data
8 bit
Parity
None
Stop bit
1 bit
Flow Control
None
7.
Login. (The default Log in values are: User: TOSHIBA, Password: ADMIN)
8.
The RemotEye 4 Configuration Utility main menu will be displayed. See Figure 4-5.
Figure 4-4 Serial Port Setup