84
RemotEye 4 User Manual – 90988-007
FAULT RECORDS PAGE
This table lists the detailed history of faults that have occurred on the UPS. The Log can store a maximum of 680
records. If more events are recorded, the new record replaces the oldest record.
T1000 & 1600XP/XPi Fault Records Log Format
Log Date – This field shows the date of the recording.
Log Time - This field shows the time that the values were recorded. Time is displayed in the hh:mm:ss 24-
hour format (i.e., 8:30 p.m. is 20:30:00).
Record Number - Maximum number of records is 255.
System Input Type
System Output Type
Input Voltage
Output Voltage
Output Load
DC Input Voltage
Battery Voltage
Slot Location
Fault
4300 Fault Records Log Format
Log Date – This field shows the date of the recording.
Log Time - This field shows the time that the values were recorded. Time is displayed in the hh:mm:ss 24-
hour format (i.e., 8:30 p.m. is 20:30:00).
Record Number – Maximum number of record is 255.
Fault 1 – Description of fault detected.
Fault 2 – Description of fault detected.
4400/5000 NEMA 3R Records Log Format
Record Number – Unique identification associated with each record. Up to 64 records held in UPS
EEPROM
Fault Code – 2 byte (4 digit) hex code that denotes which warning or fault has occurred. See Table 10-3 for
code descriptions.
Year – The year in which the fault occurred
Month – The month in which the fault occurred
Day – The day on which the fault occurred
Hour – The hour in which the fault occurred
Min – The minute in which the fault occurred
Sec – The second in which the fault occurred
Table 10-3 4400/ 5000 NEMA 3R Series Fault Codes
Code (Hex)
Fault
Warning
Description
1st byte
2nd byte
00
45
x
AC INPUT VOLTAGE OUT OF RANGE
00
47
x
AC INPUT FREQUENCY OUT OF RANGE
00
49
x
AC INPUT PHASE ROTATION ERROR
00
4D
x
INVERTER OVERLOAD
00
4F
x
INVERTER OVERLOAD
00
51
x
INVERTER CURRENT LIMIT
00
5F
x
BATTERY VOLTAGE ABNORMAL
00
55
x
COOLING FAN ABNORMAL
Summary of Contents for RemotEye 4
Page 1: ...RemotEye 4 User Manual Document Number 90988 007 September 2018 ...
Page 4: ...4 RemotEye 4 User Manual 90988 007 This Page Intentionally Left Blank ...
Page 12: ...12 RemotEye 4 User Manual 90988 007 This Page Intentionally Left Blank ...
Page 28: ...28 RemotEye 4 User Manual 90988 007 Figure 3 6 RemotEye 4 in 5000 Series 30kVA ...
Page 97: ...RemotEye 4 User Manual 90988 007 97 Figure 11 10 VM Remote Shutdown Test ...
Page 221: ...RemotEye 4 User Manual 90988 007 221 ...
Page 261: ......