RemotEye 4 User Manual – 90988-007
131
A.3
MODBUS (3X) INPUT REGISTERS FOR SINGLE PHASE UPS: MONITORING
All Registers – Size: 16-Bit, Access: Read-Only.
Note:
The Modbus registers table style addressing is protocol base 0. If monitoring software uses PLC style addressing base 1, add one to the register number. For
example, Modbus address 30001 becomes PLC address 30002 ; address 10001 becomes PLC address 10002.
Note 2:
Please make sure the latest RemotEye 4 firmware revision is installed in order to use the Modbus register table below. If not, there will be inconsistencies
between RemotEye 4 internal register addressing and this manual. Go to www.toshibaups.com to get the latest RemotEye 4 firmware.
MODBUS (3X) INPUT REGISTERS – SINGLE PHASE PLATFORMS
Registers
Data Type
Description
Units
1600XP(i)
T1000
T1000 (1-3kVA)
Multi
Supp
Multi
Supp
Multi
Supp
RemotEye
4
Sys
tem
In
for
mati
on
30001
Unsigned Integer
RemotEye 4 Software Version
Firmware
X 0.01
Y
X 0.01
Y
X 0.01
Y
30002
Unsigned Integer
RemotEye 4 Slave ID Number
ID
X 1
Y
X 1
Y
X 1
Y
30003
Unsigned Integer
IP Address First Byte
IP Address
X 1
Y
X 1
Y
X 1
Y
30004
Unsigned Integer
IP Address Second Byte
IP Address
X 1
Y
X 1
Y
X 1
Y
30005
Unsigned Integer
IP Address Third Byte
IP Address
X 1
Y
X 1
Y
X 1
Y
30006
Unsigned Integer
IP Address Fourth Byte
IP Address
X 1
Y
X 1
Y
X 1
Y
30007
Unsigned Integer
Subnet Mask First Byte
Subnet
Mask
X 1
Y
X 1
Y
X 1
Y
30008
Unsigned Integer
Subnet Mask Second Byte
Subnet
Mask
X 1
Y
X 1
Y
X 1
Y
30009
Unsigned Integer
Subnet Mask Third Byte
Subnet
Mask
X 1
Y
X 1
Y
X 1
Y
30010
Unsigned Integer
Subnet Mask Fourth Byte
Subnet
Mask
X 1
Y
X 1
Y
X 1
Y
30011
Unsigned Integer
Gateway IP Address First Byte
IP Address
X 1
Y
X 1
Y
X 1
Y
30012
Unsigned Integer
Gateway IP Address Second Byte
IP Address
X 1
Y
X 1
Y
X 1
Y
30013
Unsigned Integer
Gateway IP Address Third Byte
IP Address
X 1
Y
X 1
Y
X 1
Y
30014
Unsigned Integer
Gateway IP Address Fourth Byte
IP Address
X 1
Y
X 1
Y
X 1
Y
30015
Unsigned Integer
RemotEye 4 Installation Date
Month
X 1
Y
X 1
Y
X 1
Y
30016
Unsigned Integer
RemotEye 4 Installation Date
Day
X 1
Y
X 1
Y
X 1
Y
30017
Unsigned Integer
RemotEye 4 Installation Date
Year
X 1
Y
X 1
Y
X 1
Y
30018
Unsigned Integer
Date on RemotEye 4
Month
X 1
Y
X 1
Y
X 1
Y
30019
Unsigned Integer
Date on RemotEye 4
Day
X 1
Y
X 1
Y
X 1
Y
30020
Unsigned Integer
Date on RemotEye 4
Year
X 1
Y
X 1
Y
X 1
Y
30021
Unsigned Integer
Time on RemotEye 4
Hour
X 1
Y
X 1
Y
X 1
Y
30022
Unsigned Integer
Time on RemotEye 4
Minute
X 1
Y
X 1
Y
X 1
Y
30023
Unsigned Integer
Time on RemotEye 4
Seconds
X 1
Y
X 1
Y
X 1
Y
Summary of Contents for RemotEye 4
Page 1: ...RemotEye 4 User Manual Document Number 90988 007 September 2018 ...
Page 4: ...4 RemotEye 4 User Manual 90988 007 This Page Intentionally Left Blank ...
Page 12: ...12 RemotEye 4 User Manual 90988 007 This Page Intentionally Left Blank ...
Page 28: ...28 RemotEye 4 User Manual 90988 007 Figure 3 6 RemotEye 4 in 5000 Series 30kVA ...
Page 97: ...RemotEye 4 User Manual 90988 007 97 Figure 11 10 VM Remote Shutdown Test ...
Page 221: ...RemotEye 4 User Manual 90988 007 221 ...
Page 261: ......