174
RemotEye 4 User Manual – 90988-007
C.2
BACNET BINARY INPUT POINT MAPPING FOR 4300
ALL – BACnet Object:
Binary Input
BACnet Property:
Present Value
Out of Service:
FALSE
Access:
Read Only
Status Flags:
Normal
4300 BACnet Binary Input Point Mapping
Inst. ID
Object Name & Description
Units
Comments
RM
TI
-4
St
atus
1
RemotEye 4 Data Link
True/False (1/0)
0 = Link Up; 1 = Link Down
2
RemotEye 4 Network Link
True/False (1/0)
0 = Link Up; 1 = Link Down
UPS
M
od
e
3
Online Mode
True/False (1/0)
4
Backup Mode
True/False (1/0)
5
Bypass Mode
True/False (1/0)
6
Shutdown Mode
True/False (1/0)
Battery
Sta
tu
s
7
UPS Battery Status Unknown
True/False (1/0)
8
UPS Battery Status Normal
True/False (1/0)
9
UPS Battery Status Low
True/False (1/0)
10
UPS Battery Status Depleted
True/False (1/0)
11
UPS Battery Status Discharging
True/False (1/0)
12
UPS Battery Status Test Failure
True/False (1/0)
Batt
.
Ch
rg
St
atus
13
Protective Charging Set
True/False (1/0)
14
Equalized Charging Set
True/False (1/0)
Batt
.
Te
st
15
Battery Test Disabled
True/False (1/0)
16
Battery Test in Progress
True/False (1/0)
EMD
17
EMD Enabled
True/False (1/0)
18
EMD Alarm-1
True/False (1/0)
0 = no Alarm; 1 = Alarm Triggered
(upsAlarmEMDSensor1AlarmTriggered)
19
EMD Alarm-2
True/False (1/0)
0 = no Alarm; 1 = Alarm Triggered
(upsAlarmEMDSensor2AlarmTriggered)
Summary of Contents for RemotEye 4
Page 1: ...RemotEye 4 User Manual Document Number 90988 007 September 2018 ...
Page 4: ...4 RemotEye 4 User Manual 90988 007 This Page Intentionally Left Blank ...
Page 12: ...12 RemotEye 4 User Manual 90988 007 This Page Intentionally Left Blank ...
Page 28: ...28 RemotEye 4 User Manual 90988 007 Figure 3 6 RemotEye 4 in 5000 Series 30kVA ...
Page 97: ...RemotEye 4 User Manual 90988 007 97 Figure 11 10 VM Remote Shutdown Test ...
Page 221: ...RemotEye 4 User Manual 90988 007 221 ...
Page 261: ......