190
RemotEye 4 User Manual – 90988-007
E.2
BACNET BINARY INPUT POINT MAPPING FOR G9000/G2020
ALL – BACnet Object:
Binary Input
BACnet Property:
Present Value
Out of Service:
FALSE
Access:
Read Only
Status Flags:
Normal
G9000/G2020 BACnet Binary Input Point Mapping
Inst. ID Object Name & Description
Units
Comments
RM
TI
-4
St
atus
1
RemotEye 4 Data Link
True/False (1/0)
0 = Link Up; 1 = Link Down
2
RemotEye 4 Network Link
True/False (1/0)
0 = Link Up; 1 = Link Down
UPS
Mode
3
Online Mode
True/False (1/0)
4
Backup Mode
True/False (1/0)
5
Bypass Mode
True/False (1/0)
Battery
St
atus
6
UPS Battery Status Unknown
True/False (1/0)
7
UPS Battery Status Normal
True/False (1/0)
8
UPS Battery Status Low
True/False (1/0)
9
UPS Battery Status Depleted
True/False (1/0)
10
UPS Battery Status Discharging
True/False (1/0)
EMD
11
EMD Enabled
True/False (1/0)
12
EMD Alarm-1
True/False (1/0)
0 = no Alarm; 1 = Alarm Triggered (upsAlarmEMDSensor1AlarmTriggered)
13
EMD Alarm-2
True/False (1/0)
0 = no Alarm; 1 = Alarm Triggered (upsAlarmEMDSensor2AlarmTriggered)
Fau
lt
s
14
Alarm Fault
True/False (1/0)
1 = One or more fault reported, see below for cause; 0 = No Faults
15
DC Bus Overcurrent Fault
True/False (1/0)
16
DC Bus Overvoltage Fault
True/False (1/0)
17
DC Bus Imbalance Fault
True/False (1/0)
18
DC Undervoltage Fault
True/False (1/0)
19
Output Undervoltage Fault
True/False (1/0)
20
Output Overvoltage Fault
True/False (1/0)
21
UPS Overheat Fault
True/False (1/0)
22
Battery Overheat Fault
True/False (1/0)
23
Battery Voltage Abnormal Fault
True/False (1/0)
24
UPS Overload Fault
True/False (1/0)
25
Inverter Overload Fault
True/False (1/0)
26
Inverter Overcurrent Fault
True/False (1/0)
Warnin
gs
27
On Bypass
True/False (1/0)
upsAlarmOnBypass
28
On Battery Mode
True/False (1/0)
upsAlarmOnBattery
29
Low Battery Level Reached Warning
True/False (1/0)
upsAlarmBatteryLow
30
Battery Overheat Warning
True/False (1/0)
upsAlarmBatteryOverheat
31
Battery Depleted Warning
True/False (1/0)
upsAlarmBatteryDepleted
Summary of Contents for RemotEye 4
Page 1: ...RemotEye 4 User Manual Document Number 90988 007 September 2018 ...
Page 4: ...4 RemotEye 4 User Manual 90988 007 This Page Intentionally Left Blank ...