G.2
BACNET BINARY INPUT POINT MAPPING FOR T1000
ALL – BACnet Object:
Binary Input
BACnet Property:
Present Value
Out of Service:
FALSE
Access:
Read Only
Status Flags:
Normal
T1000 Binary Input Point Mapping
Inst. ID
Object Name & Description
Units
Comments
RM
TI
-4
St
atus
1
RemotEye 4 Data Link
True/False (1/0)
0 = Link Up; 1 = Link Down
2
RemotEye 4 Network Link
True/False (1/0)
0 = Link Up; 1 = Link Down
UPS
M
od
e
3
Startup Mode
True/False (1/0)
4
Online Mode
True/False (1/0)
5
Backup Mode
True/False (1/0)
6
Bypass Mode
True/False (1/0)
7
Shutdown Mode
True/False (1/0)
8
Battery Test Mode
True/False (1/0)
Battery
Sta
tu
s
9
UPS Battery Status Unknown
True/False (1/0)
10
UPS Battery Status Normal
True/False (1/0)
11
UPS Battery Status Low
True/False (1/0)
12
UPS Battery Status Depleted
True/False (1/0)
13
UPS Battery Status Discharging
True/False (1/0)
14
UPS Battery Status Failure
True/False (1/0)
Batt
.
Char
ge
St
atus
15
Battery Charger Status Normal Charging
True/False (1/0)
16
Battery Charger Status Preventative Charging
True/False (1/0)
17
Battery Charger Status Stop Charging
True/False (1/0)
Battery
Test
18
Battery Test in Progress
True/False (1/0)
upsAlarmBatteryTestInProgress; 1 = Currently Testing; 0 = Not Testing
19
Ok to Perform Battery Test
True/False (1/0)
From "Last Test Result" of "UPS Battery Test" page ; 1 = Ok to perform; 0
= Test prohibited
20
Last Battery Test Result
True/False (1/0)
From "Last Test Result" of "UPS Battery Test" page ; 1 = Passed; 0 =
Failed (If no test has been performed it should be blank)
EMD
21
EMD Enabled
True/False (1/0)
From "Device Status" of "EMD Setup" page
22
EMD Alarm-1
True/False (1/0)
1 = Alarm Triggered; 2 = Alarm Triggered --> 0 = no Alarm; 1 = Alarm
Triggered (upsAlarmEMDSensor1AlarmTriggered)
23
EMD Alarm-2
True/False (1/0)
1 = Alarm Triggered; 2 = Alarm Triggered --> 0 = no Alarm; 1 = Alarm
Triggered (upsAlarmEMDSensor2AlarmTriggered)
Summary of Contents for RemotEye 4
Page 1: ...RemotEye 4 User Manual Document Number 90988 007 September 2018 ...
Page 4: ...4 RemotEye 4 User Manual 90988 007 This Page Intentionally Left Blank ...
Page 12: ...12 RemotEye 4 User Manual 90988 007 This Page Intentionally Left Blank ...
Page 28: ...28 RemotEye 4 User Manual 90988 007 Figure 3 6 RemotEye 4 in 5000 Series 30kVA ...
Page 97: ...RemotEye 4 User Manual 90988 007 97 Figure 11 10 VM Remote Shutdown Test ...
Page 221: ...RemotEye 4 User Manual 90988 007 221 ...
Page 261: ......