RemotEye 4 User Manual – 90988-007
51
4.
In the
SETTINGS
drop-down menu click on “
Modbus Settings
” the selected entry text will turn
RED
.
5.
Look in the Protocol Settings Panel titled “
Modbus Settings
”. Under “
Modbus RTU Settings
” (See Figure
5.1.
set
Modbus RTU
to “
Enabled”,
5.2.
Baud Rate
to the system baud rate (Default: 9600),
5.3.
Address
to the unit address (Default: 1).
6.
Under “
Modbus TCP/IP Settings
” set
Modbus TCP/IP
to “
Disabled”
.
7.
Click the
Set
button.
Figure 6-5 Modbus Settings for Modbus RTU
8.
Configure the
Connection Setup
with master as follows:
8.1.
Connection: Serial Port
8.2.
Port Settings: Port 1, 9600 Baud, 8Data bits, Non Parity, 1 Stop bit
8.3.
Mode: RTU
8.4.
Slave ID: 1 (There can be from 1-247 Slave units, each with a unique ID, connected to each Master unit.)
9.
Set the
Read/Write Definition
(E.g. the Read registers are 30001 – 30030)
Figure 6-6 MODbus Read/Write Definitions