RemotEye 4 User Manual – 90988-007
53
Figure 6-8 RemotEye 4 RS-485 Data and GND Cabling
The RS-485 Signal range is:
Input voltage range: 0 to 5 Volts
Output voltage range: -7 to 12 Volts
SOFTWARE CONFIGURATION:
2.
On the home page dashboard, click on the
SETTINGS
hotlink at the top of the page. This will bring up the
SETTINGS
drop-down menu . (See Figure 6-9.)
3.
In the
SETTINGS
drop-down menu click on “
Interface Settings
” the selected entry text will turn
RED
.
3.1.
If using RS-485
3.1.1.
Under “
RS-485Interface Setting
s” set
RS-485 Interface (Enable/Disable)
to “
Enabled”
, and set
Define RS-485 Interface Protocol
to “
BACnet”
.
3.1.2.
Under “
RS-232Interface Setting
s” set
RS-232 Interface (Enable/Disable)
to “
Disabled”
, and set
Define RS-232 Interface Protocol
to “
Disabled”
.
3.2.
If using RS-232
3.2.1.
Under “
RS-232Interface Setting
s” set
RS-232 Interface (Enable/Disable)
to “
Enabled”
, and set
Define RS-232 Interface Protocol
to “
BACnet”
.
3.2.2.
Under “
RS-485Interface Setting
s” set
RS-485 Interface (Enable/Disable)
to “
Disabled”
, and set
Define RS-485 Interface Protocol
to “
Disabled”
.
Figure 6-9 Interface Settings for BACnet MS/TP
4.
In the
SETTINGS
drop-down menu click on “
BACnet Settings
” the selected entry text will turn RED.
5.
Look in the Protocol Settings Panel titled “
BACnet Settings
”. (See Figure 6-10)
5.1.
Under “
BACnet MS/TP Settings
” set
BACnet MS/TP Protocol
to “
Enabled”,
5.2.
Set the
Baud Rate
to the system baud rate (Default: 9600),
5.3.
Set the
MS/TP Max Masters
(Default: 127),
5.4.
Set the
Station ID
(Default: 1).
6.
Under “
BACnet IP Settings
” set
BACnet IP
Protocol
to “
Disabled”
.
7.
Click on the
Set
button.
GND
DATA +
DATA
–
Summary of Contents for RemotEye 4
Page 1: ...RemotEye 4 User Manual Document Number 90988 007 September 2018 ...
Page 4: ...4 RemotEye 4 User Manual 90988 007 This Page Intentionally Left Blank ...
Page 12: ...12 RemotEye 4 User Manual 90988 007 This Page Intentionally Left Blank ...
Page 28: ...28 RemotEye 4 User Manual 90988 007 Figure 3 6 RemotEye 4 in 5000 Series 30kVA ...
Page 97: ...RemotEye 4 User Manual 90988 007 97 Figure 11 10 VM Remote Shutdown Test ...
Page 221: ...RemotEye 4 User Manual 90988 007 221 ...
Page 261: ......