RemotEye 4 User Manual – 90988-007
81
10
HISTORY DATA & LOGS
This menu allows the user to view UPS & RemotEye 4 log messages, such as the UPS History Summaries. The log
messages are displayed in chronological order and are used to help detect and diagnose UPS problems with the
RemotEye 4.
Table 10-1 History Log Availability
History/Log
UPS Series
T1000
1600XP/XPi
4300
4400/
5000 N3R
G9000/
G2020
T1000
(1-3kVA)
5000
3P1
UPS History Summary Page
(See Section 10.1)
N/A
N/A
N/A
General Records Log
Y
Y
Y
Y
N/A
Y
N/A
Extended General Records Log
Y
Y
Y
Y
Y
Y
Y
UPS Events Log
Y
Y
Y
Y
Y
Y
Y
UPS History Log
N/A
N/A
N/A
N/A
Y
N/A
Y
UPS Extended Log
N/A
N/A
N/A
N/A
Y
N/A
Y
Test Log
Y
Y
N/A
N/A
N/A
N/A
N/A
Backup Log
Y
Y
Y
Y
N/A
N/A
Y
Fault Log
Y
Y
Y
Y
N/A
N/A
Y
Operation Log
Y
Y
Y
Y
N/A
N/A
Y
Warning Log
Y
Y
N/A
Y
N/A
N/A
Y
System Setting Log
Y
Y
N/A
N/A
N/A
N/A
Y
RemotEye 4 Events Log
Y
Y
Y
Y
Y
Y
N/A
Acknowledged Alerts Records Page
Y
Y
Y
Y
Y
Y
Y
EMD History Log
Y
Y
Y
Y
Y
Y
N/A
EMD Extended History Log
Y
Y
Y
Y
Y
Y
N/A
UPS HISTORY SUMMARY SUMMARY PAGE
This page shows UPS historical information available from various UPS models. This information is based on data
accumulated since the start of the UPS. Models having a particular record are noted in each entry.
Table 10-2 UPS History Summary Page Availability
UPS History
Meaning
T1000
1600XP/
XPi
4300
4400/5000
N3R
System Operation Time
(Secs)
Specifies how long the UPS has been operating
(includes On-Line, Bypass, Backup) in seconds.
Y
Y
Y
Y
Inverter Operation Time
(Secs)
Specifies how long the UPS has been running in
Inverter (On-Line) mode in seconds.
Y
Y
Y
Y
Backup Operation Time
(Secs)
Sspecifies how long the UPS has been running in
battery backup mode in seconds.
Y
Y
N/A
Y
Lifetime Remaining
(Months)
Specifies the remaining lifetime of the UPS in month.
Y
Y
N/A
N/A
Highest System Temp
(
C)
Shows the highest system temperature recorded of the
UPS in Celsius.
Y
Y
N/A
N/A
Highest Battery Temp
Shows the highest battery temperature recorded of the
UPS in Celsius.
Y
Y
N/A
N/A
Total Number Input
Under Voltage
Shows the total number of times the UPS has entered
under voltage state.
Y
Y
N/A
N/A
Total Number Overload
Shows the total number of times the UPS has
overloaded.
Y
Y
N/A
N/A
Total Number Test
Shows the total number of tests that has been
conducted on the UPS.
Y
Y
N/A
N/A
Total Number Backup
Shows the total number of times the UPS has switched
to battery backup mode.
Y
Y
Y
Y
Total Number Faults
Shows the total number of faults the UPS has
encountered.
Y
Y
Y
-
Summary of Contents for RemotEye 4
Page 1: ...RemotEye 4 User Manual Document Number 90988 007 September 2018 ...
Page 4: ...4 RemotEye 4 User Manual 90988 007 This Page Intentionally Left Blank ...
Page 12: ...12 RemotEye 4 User Manual 90988 007 This Page Intentionally Left Blank ...
Page 28: ...28 RemotEye 4 User Manual 90988 007 Figure 3 6 RemotEye 4 in 5000 Series 30kVA ...
Page 97: ...RemotEye 4 User Manual 90988 007 97 Figure 11 10 VM Remote Shutdown Test ...
Page 221: ...RemotEye 4 User Manual 90988 007 221 ...
Page 261: ......