92
RemotEye 4 User Manual – 90988-007
11.1.2
Setup Procedure for RemotEye ESXi Client Shutdown Daemon*
* Daemon – A program on Unix/Linux-like operating systems that runs unobtrusively in the background, waiting to be activated by the occurrence of a specific event
or condition.
1.
Confirm that ESXi is a Full or Evaluation version. (The Free version does not support this function.)
2.
If vMA is already installed in ESXi skip to Step 7. Otherwise, download vMA OS (SUSE OS) from the
Downloads section of the VMware website,
3.
Install vMA OS (SUSE OS) on ESXi server by navigating to
File > Deploy OVF Template
and follow the
instructions.
4.
Run the vMA OS.
Note: Default username is
vi-admin
. When prompted for the password, just press the
Enter
key.
5.
Change the vMA settings. Ensure RemotEye has access to the vMA network. (Example: Assign the IP to
10.2.0.11)
6.
Create the Super User password:
6.1.
Type “
sudo passwd”
into the command line prompt and press
Enter
. Follow the instructions to create
the root password.
6.2.
Type “
su root”
into command prompt and press
Enter.
Follow the instructions to log in as root.
Note:
When logged in as Super User, text color turns
RED
.
(S
Figure 11-2 Text turns RED in Super User Mode
7.
Add the server to vMA using “
vfip addserve
r [ESXi Server IP]”, then enter the ESXi password. (Example:
IP=10.1.10.220) (See Figure 11-3)
Figure 11-3 Add Server to vMA
8.
Confirm ESXi was added to vMA: On the command line type “
vifp listservers
”
and press
Enter.
The
command returns:
10.1.10.220 ESXi
Figure 11-4 ESXi Added to VMA
9.
Enable SSH in vMA (if not Enabled).
9.1.
On the command line prompt type: “
vi /etc/hosts.allow
” and press
Enter
.
9.2.
Type “
l
” and press
Enter
.
(edits file)
9.3.
Type “
sshd: ALL: ALLOW
” and press
Enter
.
9.4.
Press the
ESC
key.
9.5.
Type “
w
” and press
Enter
. (writes to file)
9.6.
Type “
q
” and press
Enter
. (exits file)
Summary of Contents for RemotEye 4
Page 1: ...RemotEye 4 User Manual Document Number 90988 007 September 2018 ...
Page 4: ...4 RemotEye 4 User Manual 90988 007 This Page Intentionally Left Blank ...
Page 12: ...12 RemotEye 4 User Manual 90988 007 This Page Intentionally Left Blank ...
Page 28: ...28 RemotEye 4 User Manual 90988 007 Figure 3 6 RemotEye 4 in 5000 Series 30kVA ...
Page 97: ...RemotEye 4 User Manual 90988 007 97 Figure 11 10 VM Remote Shutdown Test ...
Page 221: ...RemotEye 4 User Manual 90988 007 221 ...
Page 261: ......