98
RemotEye 4 User Manual – 90988-007
11.1.3
Toshiba UPS Shutdown Events Setup
RemotEye 4 can help further protect critical load systems connected to a UPS by initiating automated shutdowns on
that equipment. RemotEye 4 can shutdown servers/clients upon detection of UPS events: Input Power Failure,
Battery Low, UPS Overload, UPS System Overheat, EMD Temperature Over Threshold, EMD Alarm-1, EMD
Alarm-2, Recurring On/Off Schedule, and Non-Recurring On/Off Schedule. Also, RemotEye 4 can be used to
coordinate automatic system shutdowns during weekends or holidays. This section highlights the manners in which
RemotEye 4 can be used in conjunction with a UPS to manage power to UPS loads.
11.1.3.1
UPS Shutdown Events
RemotEye 4 can initiate output shutdown upon the occurrence of nine different UPS events Input Power Failure,
Low Battery, UPS Overload, UPS System Overheat, EMD Temperature Over Threshold, EMD Alarm-1, EMD
Alarm-2, Recurring On/Off Schedule and Non-recurring On/Off Schedule. Users can view the current setting of
these events in the
UPS Shutdown Events
widget on the RemotEye 4 Dashboard, or web page
UPS
MANAGEMENT
→
UPS Shutdown Events
. See Table 5-2 Widget Parameter List by Product Line.
To alter these settings, log in as an administrator, and configure the UPS shutdown events action and delay times
accordingly. Click the Set Value button when finished.
Scenario:
Shutdown Event:
Input Power Failure
Action:
Client Shutdown
Shutdown Delay (sec):
420 (default)
Broadcast Notification (sec):
30 (default)
UPS Output Shutdown Delay (Sec):
180 (default)
UPS Events - AC failed
22:20:00
22 : 20 : 00
22 : 27 : 00 22 : 30 : 00
Client’s local shutdown delay (Sec):
120(default)
22 : 20 : 00
22 : 27 : 00 22 : 29 : 00
INVERTER
OUTPUT
SHUTDOWN
CLIENT ON
CLIENT OFF
Summary of Contents for RemotEye 4
Page 1: ...RemotEye 4 User Manual Document Number 90988 007 September 2018 ...
Page 4: ...4 RemotEye 4 User Manual 90988 007 This Page Intentionally Left Blank ...
Page 12: ...12 RemotEye 4 User Manual 90988 007 This Page Intentionally Left Blank ...
Page 28: ...28 RemotEye 4 User Manual 90988 007 Figure 3 6 RemotEye 4 in 5000 Series 30kVA ...
Page 97: ...RemotEye 4 User Manual 90988 007 97 Figure 11 10 VM Remote Shutdown Test ...
Page 221: ...RemotEye 4 User Manual 90988 007 221 ...
Page 261: ......