RemotEye 4 User Manual – 90988-007
99
11.1.3.2
Managing the UPS On/Off Schedule (Applicable to 1600XP/XPi Only)
RemotEye 4 supports two output shutdown schedules – (1) Recurring Schedule; (2) Non-recurring Schedule.
Note: Before managing the UPS Shutdown Schedule, please make sure that the Date and Time configured in
RemotEye 4 is correct. To access recurring or non-recurring schedule go to
UPS MANAGEMNT
→
UPS On/Off
Schedule
web page.
Scenario:
UPS Event:
Recurring On/Off Schedule
Action:
UPS Output & Client shutdown
Shutdown Delay (sec):
600(default)
Broadcast Notification (sec):
60(default)
UPS Output Shutdown Delay (Sec):
180(default)
Shutdown & Restart day & time:
Monday 22:20:00 ----- 99:99:99
Shutdown & Restart day & time:
Tuesday 99:99:99 ----- 09:00:00
Note: 99:99:99 indicates the RemotEye 4 will ignore the Restart Time on Monday, and the Shutdown time on
Tuesday.
Monday
Tuesday
22 : 20 : 00 22 : 30 : 00 22 : 33 : 00 09:00:00
INVERTER
OUTPUT
SHUTDOWN