27
Address Setup
<Clearing Indoor Unit address>
U3 U4
U1 U2
U5 U6
U1 U2
A B
U3 U4
U1 U2
U5 U6
U1 U2
A B
U3 U4
U1 U2
U5 U6
U1 U2
A B
U3 U4
U1 U2
U5 U6
U1 U2
A B
U3 U4
U1 U2
U1
U3
U2
U4
U5 U6
U1 U2
A B
Central remote
controller
Header
unit
Follower unit
Follower unit
Remote
controller
Remote
controller
Remote
controller
Remote
controller
Indoor units to have their addresses initialized
Header
unit
Header
unit
Method 1
Clearing each address separately using a wired remote controller.
Set the system address, indoor unit address and group address to “
” using a wired remote controller.
(For the setting procedure, refer to the address setting procedures using the wired remote controller on the previ-
ous pages.)
Method 2
Clearing all the indoor unit addresses on a refrigerate line at once from the outdoor unit.
1
Turn off the refrigerant line to reset to the factory default and set the header outdoor unit of the line as below.
2
Turn on the indoor and outdoor units of the refrigerant line for which you want to initialize the ad-
dresses. About one minute after turning on the power, confirm that the 7-segment display on the header
outdoor unit indicates “ U.1. - - -” and operate the interface P.C. board on the header outdoor unit of the
refrigerant line as follows.
3
Confirm that the 7-segment display indicates “ A.d. c.L.” and set SW01, SW02 and SW03 to 1, 1, 1 respec-
tively.
4
After a time “ U.1.L08” appears on the 7-segment display if the address clearing has been completed
successfully.
If the 7-segment display indicates “ A.d. n.G.” , the outdoor unit may still connected with other refrigerant
lines. Check the connection of the relay connectors between [U1, U2] and [U3, U4].
NOTE
Take care to carry out the procedure above correctly; otherwise, addresses in other refrigerate lines may also
be cleared.
5
Set the addresses again after finishing the clearance.
1) Disconnect the relay connectors between the [U1, U2] and [U3, U4] terminals.
(Leave them as they are if they have already been disconnected.)
2) Turn on dip switch 2 of SW30 on the interface P.C. board of the header outdoor
unit if the switch is OFF.
(Leave it as it is if it has already been set to ON.)
s
e
s
s
e
r
d
d
a
e
l
b
a
r
a
e
l
C
4
0
W
S
3
0
W
S
2
0
W
S
1
0
W
S
2
1
2
Confirm that the 7-segment display indicates
“A.d.buS” and turn SW04 ON for more than five
seconds.
System/indoor unit/group address
2
2
2
Confirm that the 7-segment display indicates
“A.d.nEt” and turn SW04 ON for more than five
seconds.
Central control address
Resetting the address (Resetting to he factory default (address undecided)
Summary of Contents for SMMS-e