36
Troubleshooting
in Test Operation
<Cooling, Heat pump type>
Operation from the indoor remote controller is not accepted, and a Check Code is
displayed on the 7 - seqment display of the interface PC board of header unit.
There is no display of a Check Code on the 7 - segment display on the interface PC
boardof the header unit, although there is indoor unit that is not accepting operation
from the indoor remote controller.
Indoor remote
controller
status
Header unit
7-segment
display
s
e
r
u
s
a
e
m
r
e
t
n
u
o
C
e
s
u
a
C
No response
L08
Line addresses and indoor addresses of all the connected
indoor units are not set.
Set up addresses.
There is no header unit of group control.
Set up a group address.
E19 -00
Alternate
blinking
:
r
e
d
r
o
e
h
t
n
I(
.
n
i
a
g
a
r
e
w
o
p
e
h
t
n
o
n
r
u
T
.
n
o
d
e
n
r
u
t
t
o
n
s
i
r
e
w
o
p
t
i
n
u
r
o
o
d
n
I
indoor
→
outdoor)
Indoor/outdoor communication line is not correctly connected
to the U1/U2 terminal of the header unit. (Fig 1)
(Indoor / outdoor cannot communicate before address setup.)
Correct wiring
There is no of outdoor terminal resistance, or there
are two or more resistances (before address setup).
Check SW30 bit 2 of the header unit.
No connection between multiple refrigerant
lines: SW30 bit 2 is on.
Connection between multiple refrigerant
lines: SW30 bit 2 of the connected header
unit is turned on only for one line.
E19 -02
Alternate
blinking
When connecting an indoor/outdoor communication line
between outdoor units under the condition of a connected
communication line between outdoor units. (Fig 2)
Correct wiring
E20 -01
Alternate
blinking
Address setup is performed with connecting an indoor/
outdoor communication line between outdoor units. (Fig 3)
Correct wiring
Address setup is performed under the condition of
connecting multiple refrigerant lines. (Fig 3)
Correct wiring
ON
1
2
SW30
Indoor remote
controller
status
Header unit
7-segment
display
s
e
r
u
s
a
e
m
r
e
t
n
u
o
C
e
s
u
a
C
No response
None
The communication line is not connected between indoor
and outdoor (the unit that does not respond to the indoor
remote controller).
Modify the wiring.
Line address and indoor address are not set (the unit that
does not respond to the indoor remote controller).
Set up the address.
The power of the header unit of the group is not turned on in
indoor group control (the unit that does not respond to the
indoor remote controller).
Turn on the power.
Group address is set to the follower unit for individual control
(the unit that does not respond to the indoor remote
controller).
Set the group address to “0” in the case of
individual control.
No display on the
indoor remote
controller (no line
is output.)
None
The power is not turned on (the unit that is not displayed on
the indoor remote controller).
Turn on the power.
The indoor remote controller is not connected with a wire (the
unit that is not displayed on the indoor remote controller).
Modify the wiring.
Miswiring of the indoor remote controller (the unit that is not
displayed on the indoor remote controller)
Modify the wiring.
Indoor remote controller communication circuit trouble (the
unit that is not displayed on the indoor remote controller)
If 220-240 V is incorrectly applied to the indoor remote
controller terminal, the remote controller communication
circuit fails.
Remove the Faston connect terminal
connected to indoor remote controller
terminals A/B, and check the voltage. If
voltage is not applied (normally 15 to 18 V),
replace the PC board.