37
Troubleshooting
in Test Operation
In checking the number of connected outdoor units and connected indoor unit after address
setup, a lower number of connected units is displayed.
(There are outdoor/indoor units that do not operate in a test operation.)
s
e
r
u
s
a
e
m
r
e
t
n
u
o
C
e
s
u
a
C
s
u
t
a
t
S
The number of
connected
outdoor units is
too few.
Miswiring of communication lines between outdoor units
or an unconnected wire ( Fig. 4).
(Address setup operation finished without recognizing a
miswired follower unit.)
After modification of wiring, set up the addresses again and
check the number of connected outdoor units.
The number of
connected indoor
units is too few.
Miswiring of communication lines between indoor units
or an unconnected wire. (Fig 5)
(Address setup operation finished without recognizing a
miswired indoor unit.)
After modification of wiring, set up the addresses again and
check the number of connected indoor units.
The number of
outdoor units
connected to a
group is too few in
group operation
from an indoor
remote controller.
The indoor remote controller is not connected with wire.
Miswiring of the indoor remote controller
Using the main indoor remote controller connected to a group,
start a test operation, specify the unit that is not operating (the
unit not connected to the group), and then check the wiring.
Indoor remote controller communication circuit trouble
If 220-240 V is incorrectly applied to the remote
controller terminal, the remote controller communication
circuit fails.
Using the main indoor remote controller connected to a group,
start a test operation and then specify the unit that is not
operating (the unit not connected to the group). Remove the
Faston connect terminal connected to remote controller
terminals A/B, and check the voltage. If voltage is not applied
(normally 15 to18 V), replace the PC board.
<Cooling, Heat pump type>
Summary of Contents for SMMS-e
Page 96: ...Quick Reference ...