DK424 Installation
Reserve Power Installation
Strata DK I&M 6/00
5-37
DK424 Installa
tion
CAB 1
CAB 2
CAB 3
CAB 4
CAB 5
CAB 6
CAB 7
RPSB1A
RPSB1A
RPSB2A
RPSU280A
RPSU280A
AC IN
AC IN
RPSU280A
AC IN
RPSU280A
AC IN
RPSU280A
AC IN
RPSU280A
MBJU
(see Note below)
Jumper Unit
AC IN
RPSU280A
AC IN
FG
FG
FG
FG
FG
FG
FG
2044
AC Cable
Intercabinet Power
Supply Ground Wire
Frame Ground
Screw (FG)
Data Cables
115VAC ± 10VAC
(50/60 Hz)
(7.5 Amp max)
Insulated
Ground
Wire “B”
Earth Ground:
Cold Water Pipe
or Ground Rod
AWG #6 Wire
Maximum
Length: 60 Feet
Per General Rules
of Article 250 of
the National
Electric Code,
NFPA70
ONEAC 6-AP
or 6-DP
Solid State
Secondary
Protectors
Third Wire
AC Ground
Building Main Power
Panel Electrical Ground
“A”
115VAC ± 10VAC (50/60 Hz)
Dedicated 20 Amp
Branch Circuit
115VAC ± 10VAC
(50/60 Hz)
(10 amp max)
Seventh cabinet data cable
(order part # RC7C1A-1.7m)
Third Wire Ground
to AC Power
Figure 5-22 AC Power Distribution for Seven Cabinets
Important!
Remove MBJU only when RCTUE/F is installed.
Summary of Contents for Strata AirLink DK40i
Page 22: ...Introduction Related Documents Media xx Strata DK I M 6 00 ...
Page 48: ...DK14 Installation DK14 Wiring Diagrams 1 26 Strata DK I M 6 00 ...
Page 220: ...DK424 Installation Remote Cabinet Installation Instructions 5 68 Strata DK I M 6 00 ...
Page 262: ...DK424i Configuration Primary Reserve Power Cabinet Hardware 6 42 Strata DK I M 6 00 ...
Page 450: ...Universal Slot PCB Wiring Option Interface PCB Wiring Diagrams 10 42 Strata DK I M 6 00 ...
Page 592: ...Peripheral Installation Enhanced 911 Service E911 12 84 Strata DK I M 6 00 ...
Page 616: ...ACD Installation Spectrum Electronic Wall Boards 13 24 Strata DK I M 6 00 ...
Page 634: ...Fault Finding Fault Isolation Flowcharts 14 18 Strata DK I M 6 00 ...
Page 704: ...ISDN Interfaces ISDN Disconnect Cause Code 16 54 Strata DK I M 6 00 ...