1
3
4
( )
Refrigerant overcharge,
clogging, pipe breakage,
abnormal overload condition
Heating operation
Check indoor P.C. board.
Failure
→
Replace
Repair
faulty parts.
Replace TC2
or TCJ sensor.
Replace PMV body.
Is SV4 circuit normal?
Is SV5 circuit normal?
Are connector connection,
heat exchanger, fan, and
fan motor normal?
Are characteristics of TC2
and TCJ sensor resistance
value normal?
Is connector
connection,
coil normal?
Repair SV4 circuit.
Coil error, clogging,
disconnection of wiring, etc.
Are not indoor units of different
refrigerant circuit connected?
Is there clogging
of valve?
Is indoor
PMV normal?
Does heating indoor fan
normally operate?
Repair
faulty parts.
A
C
Repair faulty position.
Connector connection,
cabling, coil installation,
clogging, etc
Refrigerant overcharge,
clogging,pipe breakage,
abnormal overload condition
Check and
correct the cabling.
(Check with miscabling check function of outdoor unit.)
Eliminate the
interfered causes.
Is there a cause to
interfere operation of
indoor heat exchanger?
1 Air filter clogging
2 Heat exchanger clogging
3 Air short circuit
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
FILE NO. SVM-1
40
77