30
SMMS High-Wall Type
SMMS High-Wall Type
Installation Manual
Installation
• Install the air conditioner securely in a location where the base can sustain the weight adequately. If the
strength is not enough, the unit may fall down resulting in injury.
• Follow the instructions in the Installation Manual to install the air conditioner. Failure to follow these instructions
may cause the product to fall down or topple over or give rise to noise, vibration, water leakage or other
trouble.
• Carry out the specied installation work to guard against the possibility of high winds and earthquake. If the air
conditioner is not installed appropriately, a unit may topple over or fall down, causing an accident.
• If refrigerant gas has leaked during the installation work, ventilate the room immediately. If the leaked
refrigerant gas comes in contact with fire, noxious gas may generate.
• Use forklift to carry in the air conditioner units and use winch or hoist at installation of them.
Refrigerant piping
• Install the refrigerant pipe securely during the installation work before operating the air conditioner. If the
compressor is operated with the valve open and without refrigerant pipe, the compressor sucks air and the
refrigeration cycles is over pressurized, which may cause a injury.
• Tighten the flare nut with a torque wrench in the specified manner. Excessive tighten of the flare nut may
cause a crack in the flare nut after a long period, which may result in refrigerant leakage.
• After the installation work, confirm that refrigerant gas does not leak. If refrigerant gas leaks into the room and
flows near a fire source, such as a cooking range, noxious gas may be generated.
• When the air conditioner has been installed or relocated, follow the instructions in the Installation Manual and
purge the air completely so that no gases other than the refrigerant will be mixed in the refrigerating cycle.
Failure to purge the air completely may cause the air conditioner to malfunction.
• Nitrogen gas must be used for the airtight test.
• The charge hose must be connected in such a way that it is not slack.
Electrical wiring
• Only a qualified installer(*1) or qualified service person(*1) is allowed to carry out the electrical work of the air
conditioner. Under no circumstances must this work be done by an unqualified individual since failure to carry
out the work properly may result in electric shocks and/or electrical leaks.
• To connect the electrical wires, repair the electrical parts or undertake other electrical jobs, wear gloves to
provide protection for electricians and from heat, insulating shoes and clothing to provide protection from
electric shocks. Failure to wear this protective gear may result in electric shocks.
• Use wiring that meets the specifications in the Installation Manual and the stipulations in the local regulations
and laws. Use of wiring which does not meet the specifications may give rise to electric shocks, electrical
leakage, smoking and/or a fire.
• Connect earth wire. (grounding work)
Incomplete grounding causes an electric shock.
• Do not connect earth wires to gas pipes, water pipes, and lightning conductor or telephone earth wires.
• After completing the repair or relocation work, check that the earth wires are connected properly.
• Install a circuit breaker that meets the specifications in the installation manual and the stipulations in the local
regulations and laws.
• Install the circuit breaker where it can be easily accessed by the agent.
• When installing the circuit breaker outdoors, install one which is designed to be used outdoors.
• Under no circumstances the power wire must not be extended. Connection trouble in the places where the
wire is extended may give rise to smoking and/or a fire.
• Electrical wiring work shall be conducted according to law and regulation in the community and installation
manual. Failure to do so may result in electrocution or short circuit.
Test run
• Before operating the air conditioner after having completed the work, check that the electrical control box
cover of the indoor unit and service panel of the outdoor unit are closed, and set the circuit breaker to the ON
position. You may receive an electric shock if the power is turned on without first conducting these checks.
• If there is any kind of trouble (such as an error display has appeared, smell of burning, abnormal sounds, the
air conditioner fails to cool or heat or water is leaking) has occurred in the air conditioner, do not touch the air
conditioner yourself but set the circuit breaker to the OFF position, and contact a qualified service person.
Take steps to ensure that the power will not be turned on (by marking “out of service” near the circuit breaker,
for instance) until qualified service person(*1) arrives. Continuing to use the air conditioner in the trouble status
may cause mechanical problems to escalate or result in electric shocks or other trouble.
• After the work has finished, use an insulation tester set (500 V Megger) to check the resistance is 1 MΩ or
more between the charge section and the non-charge metal section (earth section). If the resistance value is
low, a disaster such as a leak or electric shock is caused at user’s side.
• Upon completion of the installation work, check for refrigerant leaks and check the insulation resistance and
water drainage. Then conduct a test run to check that the air conditioner is operating properly.