39
SMMS High-Wall Type
Installation Manual
Toshiba
▼
In case of bottom right or bottom left piping
• After scribing slits of the front panel with a knife or a marking-off pin, cut them with a pair of nippers or an
equivalent tool.
▼
Left-hand connection with piping
Bend the connecting pipe so that it is laid within 43mm above the wall surface. If the connecting pipe is laid
exceeding 43mm above the wall surface, the indoor unit may unstably be set on the wall. When bending
the connecting pipe, make sure to use a spring bender so as not to crush the pipe.
Bend the connection pipe within a radius of 30 mm.
To connect the pipe after installation of the unit (figure)
NOTE
If the pipe is bent incorrectly, the indoor unit may unstably be set on the wall.
After passing the connecting pipe through the pipe hole, connect the connecting pipe to the auxiliary pipes
and wrap the facing tape around them.
CAUTION
• Bind the auxiliary pipes (two) and power supply wiring and control wiring with facing tape tightly. In case
of leftward piping and rear leftward piping, bind the auxiliary pipes (two) only with facing tape.
• Carefully arrange pipes so that any pipe does not stick out of the rear plate of the indoor unit.
• Carefully connect the auxiliary pipes and connecting pipes to one another and cut off the insulating tape
wound on the connecting pipe to avoid double-taping at the joint, moreover, seal the joint with the vinyl
tape, etc.
• Since dew results in a machine trouble, make sure to insulate both the connecting pipes.
(Use polyethylene foam as insulating material.)
• When bending a pipe, carefully do it, not to crush it.
Slit
570mm
Outward form of indoor unit
(To the fore front of flare)
R 30 mm (Use polish polyethylene core
or the like for bending pipe.)
Gas side
Liquid side
Use the handle of screwdriver, etc.
420mm
43
mm
80°
Power supply wiring
Indoor unit
Auxiliary pipes
Installation plate
Control wiring
+1111050501_01EN_SMMS_HighWall_IM_B5.book Page 11 Wednesday, November 12, 2008 2:45 PM
SMMS High-Wall Type
Installation Manual
Toshiba
7
INDOOR UNIT FIXING
1. Pass the pipe through the hole in the wall,
and hook the indoor unit on the installation
plate at the upper hooks.
2. Swing the indoor unit to right and left to
confirm that it is firmly hooked up on the
installation plate.
3. While pressing the indoor unit onto the wall,
hook it at the lower part on the installation
plate. Pull the indoor unit toward you to
confirm that it is firmly hooked up on the
installation plate.
• For detaching the indoor unit from the installation
plate, pull the indoor unit toward you while
pushing its bottom up at the specified parts.
REQUIREMENT
The lower part of indoor unit may float, due to the
condition of piping and you cannot fix it to the
installation plate. In that case, use the screws
provided to fix the unit and the installation plate.
Especially when the pipes are pulled out from
the left side, the unit must be screwed to the
installation plate.
8
DRAINAGE
1. Run the drain hose sloped downwards.
NOTE
• Hole should be made at a slight downward slant
on the outdoor side.
2. Put water in the drain pan and make sure
that the water is drained out of doors.
3. When connecting extension drain hose,
insulate the connecting part of extension
drain hose with shield pipe.
CAUTION
Arrange the drain pipe for proper drainage from
the unit.
Improper drainage can result in dew-dropping.
This air conditioner has the structure designed to
drain water collected from dew, which forms on the
back of the indoor unit, to the drain pan.
Therefore, do not store the power cord and other
parts at a height above the drain guide.
1
2
Press
(unhook)
Hook
Hook here
Installation plate
Push
Push
screw
screw
Do not put the
drain hose end
in the drainage
ditch.
Do not put the
drain hose end
into water.
Do not rise the drain hose.
Do not form the drain hose
into a wavy shape.
50 mm
or more
Drain hose
Inside the
room
Shield pipe
Extension drain hose
Wall
Drain guide
Space for pipes