–
21
–
FILE NO. SVM-13092
7-2. Operation Data
<Cooling>
<Heating>
NOTES :
1. Measure surface temperature of heat exchanger pipe around center of heat exchanger path U bent.
(Thermistor themometer)
2. Connecting piping condition : 5 m
Model name
Standard
Indoor
Outdoor
Compressor
RAS-
pressure
fan mode
fan mode
revolution
Indoor
Outdoor
P (MPa)
T1 (°C)
T2 (°C)
(rps)
27/19 35/-
077SKV-E6 0.9 to 1.1 13 to 14
45 to 46
High High 40
107SKV -E6 0.9 to 1.0 11 to 12 48 to 49 High High 53
137SKV -E6 0.8 to 1.0 10 to 11 48 to 49 High High 75
condition(°C)
Tempeature
Heat exchanger
pipe temp.
Model name
Standard
Indoor
Outdoor
Compressor
RAS-
pressure
fan mode
fan mode
revolution
Indoor Outdoor P (MPa)
T1 (°C)
T2 (°C)
(rps)
20/- 7/6
077SKV-E6 2.4 to 2.5 36 to 37 0 to 1 High High 51
107SKV -E6 2.4 to 2.5 40 to 41 0 to 1 High High 67
137SKV -E6 2.8 to 2.9 41 to 42 0 to 1 High High 75
condition(°C)
Tempeature
Heat exchanger
pipe temp.