There are two communications ports on the Gateway, labeled PLC1 and PLC2.  Each port can be 
configured for either RS232 or RS485 operation.  Gateway can communicate through either the T-Series 
RS232 programming port or the RS485 computer link port.   
 
 
 
 
 
Gateway is setup using simple MS Windows setup software.   The software allows devices/registers from 
one device to be mapped to devices/registers of the other device.  For Modbus, the 400001 numbered 
holding registers can be mapped directly to D data registers in the Toshiba PLC.   
 
 
 
 
 
 
 
In the above example, 5 data registers in the T1 PLC starting at D101 are written into PID controller 
modbus registers starting with holding register 400001.   3 Holding registers in the PID controller are 
written into the data registers of the T1 starting at D0 (D0 –D2).  It is also possible to control the priority 
and frequency of the data transfer using the Gateway setup software. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 

 

 
 
 

 

 

 

 

 

 

 

Page 3 

 

Power Supply: 

24 VDC +/- 5 % (50 ma MAX.) No Fuse inside 

 

5 VDC +/- 5 % FROM PLC  (120 ma MAX.) 

Communication: 

Two ports as follows: 

      

     Com 1: RS232C/RS485 

 

     Com 2: RS232C/RS485  

Status LEDs: 

PLC1 LED 

 STATUS 

LED 

   

PLC2 LED 

Temperature:  

Operating: 0 to 60 

°

C     Storage: - 40 to 90 

°

Humidity: 

10% to 90% (Non condensing) 

Immunity to ESD: 

Level 3 as per IEC1000-4-2  

Immunity to Transients: 

Level 3 as per IEC1000-4-4 

Radiated Susceptibility: 

Level 3 as per IEC1000-4-3 

Emissions: 

EN55011 CISPR A 

Dimensions: 

97mm(W) X 15.mm (H) X 42mm(D)  DIN RAIL mounting 
available 

Weight: 

100 gm Approx. 

 

    

 

Gateway Modes

 

 

Gateway Setup

 

 

Specifications

 

Summary of Contents for T1-40 PLC

Page 1: ...th Toshiba T1 40 PLC Temperature Controllers Motor Protection Relays CAN WE TALK Everyone Always Wants to Know What Everyone Else is Doing Adjustable Speed Drives Don t Let Anyone Work Alone Higher Level Controller Computer DCS PLC Programmable Controllers ...

Page 2: ...s used to map the registers between the other devices controllers to registers in the Toshiba PLC Toshiba PLC as Master on Modus Network Toshiba PLC as Slaves on Modus Network Toshiba PLC to Other PLC Connection Page 2 Description Applications Operator Interface Station Adjustable Speed Drive Modbus Temperature Controller Modbus Toshiba Protocol XY Protocol We Can Talk Now Toshiba T2 PLC Toshiba T...

Page 3: ...starting with holding register 400001 3 Holding registers in the PID controller are written into the data registers of the T1 starting at D0 D0 D2 It is also possible to control the priority and frequency of the data transfer using the Gateway setup software Page 3 Power Supply 24 VDC 5 50 ma MAX No Fuse inside 5 VDC 5 FROM PLC 120 ma MAX Communication Two ports as follows Com 1 RS232C RS485 Com 2...

Page 4: ...Connects Gateway to T2 and PC for downloading Gateway Program SC G 019A 00 Cable Connects Gateway to T1 programming port 2m SC G 019B 00 Cable Connects Gateway to T2 programming port 2m Page 4 ADJUSTABLE SPEED DRIVES MOTORS CONTROLS UPS INSTRUMENTATION PLC DCS INTERNATIONAL CORPORATION 13131 West Little York Rd Houston TX 77041 Ph 713 466 0277 Fax 713 466 8773 US 800 231 1412 Canada 800 872 2192 M...

Reviews: