G9000 Installation and Operation Manual
31
The UPS is equipped with a selectable output contact feature.
The above alarms are the default settings.
Contact Toshiba International Corporation for setup information.
B) Input Contacts (for remote access of UPS)
External contacts are provided by the user of the UPS system. Terminal voltage at the UPS is
24Vdc. Provide external dry contact accordingly.
Do not apply voltages to remote access input terminals.
Damage to UPS may result.
Refer to Figure 2.12 for a typical wiring configuration. Although this figure applies to the remote
start/stop terminals, the same wiring arrangement is used for emergency stop; power demand; and
battery temperature high.
FIGURE 2.12
Remote "Start" Contact Connections
Start
Relay Coil current : 8.3mA
Use Momentary Switches Only
UPS Cabinet
External to UPS
Cabinet
Relay
Coil
24 VDC
Start
Switch
Common
User
supplied
0.5S- 4S
ON
OFF
!
NOTE
PROHIBIT
Summary of Contents for T90S3S08KS6XSN
Page 21: ......
Page 23: ......
Page 25: ......
Page 27: ......
Page 29: ...G9000 Installation and Operation Manual ...
Page 31: ...G9000 Installation and Operation Manual ...
Page 98: ...G9000 Installation and Operation Manual 61 APPENDIX A Installation Planning Guides IPG ...
Page 99: ...62 G9000 Installation and Operation Manual ...
Page 100: ...G9000 Installation and Operation Manual 63 ...
Page 101: ...64 G9000 Installation and Operation Manual ...
Page 102: ......
Page 104: ......
Page 105: ......
Page 106: ......
Page 107: ......
Page 108: ......
Page 109: ......
Page 110: ......
Page 111: ......
Page 112: ......
Page 113: ......
Page 114: ......
Page 115: ......
Page 116: ......
Page 117: ......
Page 118: ......
Page 119: ......
Page 120: ......
Page 121: ......
Page 122: ......
Page 123: ......
Page 124: ......
Page 125: ......
Page 126: ......
Page 127: ......
Page 128: ......
Page 129: ......
Page 130: ......
Page 131: ......