Communication Conf.
(1) Display the "Communication Conf." screen
The "Communication Conf." screen appears.
(2) Press [<] [
˄
] [
˅
] [>] to select the SW number, then press [<] [
˄
] [
˅
] [>] to set SW
• Press [
˄
] and [
˅
] to change the number.
(3) Press [
] (Confirm)
The data is confirmed and the display returns to the "Servicing Menu" screen.
●
NOTE
For details of the Communication Conf., refer to the table below.
Weekly timer input switching
SW24
Timer OFF
→
ON
Timer ON
→
OFF
1
2
3
All start
All stop
0
0
0
No change
All stop
1
0
0
All indoor units are locally controllable.
All indoor units are centralized 1
0
1
0
All stop and all indoor units are centralized 1
1
1
0
All indoor units are centralized 2
0
0
1
All stop and all indoor units are centralized 2
1
0
1
SW23
No
1234 5678
SW23
0000 0000
SW24 0000 0000
SW25 0000 0000
0:
1:
Controlled unit number mode switching
(2)(3)(4)(5)
0000 = All groups
1000 = Groups 1 to 16
0100 = Groups 17 to 32
0010 = Groups 33 to 48
0001 = Groups 49 to 64
OFF
ON
Communication Conf.
SW24
Controlled unit number
mode switching (4)
0 = All groups
1 = Groups 1 to 16,
17 to 32, 33 to 48,
49 to 64
Central remote controller
Header unit switching (1)
0 = Header unit
1 = Follower unit
Weekly timer input switching (1)(2)(3)
000 = All stop
100 = All stop
010 = All indoor units are centralized 1
110 = All stop and all indoor units are centralized 1
001 = All indoor units are centralized 2
101 = All stop and all indoor units are centralized 2
SW23
1
Header
0
Follower
1
Controlled unit number
mode switching
SW23
SW24
2
3
4
5
4
All groups
0
0
0
0
0
Groups 1 to 16
1
0
0
0
1
Groups 17 to 32
0
1
0
0
1
Groups 33 to 48
0
0
1
0
1
Groups 49 to 64
0
0
0
1
1
Central remote controller header/
follower switching