Central remote controller
Installation Manual
4
-EN
4
How to perform wiring
■
Wiring specifications
Use the following wiring material to connect signal wires and power supply wires. (Locally procured)
●
NOTE
• TCC-LINK does not have polarity.
• Connect the shield of the TCC-LINK communication line to the earth on the air conditioner side. (One point earth)
CAUTION
• Turn off the power of the air conditioner for safety during installation and removal.
• Connect the power wiring to 220-240 VAC. If you wire the product incorrectly, it will fail.
• Connect the wiring correctly. If you wire the product incorrectly, it will fail.
• Do not wire communication lines (outdoor/indoor transition wiring, central control line wiring) or input/output wiring next to
power supply wiring, etc., or house them in the same metal pipe. Doing so may result in failure.
• Connect the communication line to the outdoor/indoor transition wiring or central control line wiring.
• Do not pass the communication line inside the same conduit as the power supply wiring (220 VAC, etc.), wire with the same
cable, or bring the wiring close to each other.
• For the communication line, use a signal wire that makes it possible to understand the difference between the remote
controller wiring and the power supply wiring.
• Be sure to install a breaker or an all-pole isolating switch on the primary side of the equipment side power supply of TCC-
LINK and digital input/output.
No.
Wiring
Wire type / wire diameter / wire length
1
For TCC-LINK
Microphone cord (shielded) (two-core) for instrumentation
1.25 mm
2
, up to 1000 m
2.00 mm
2
, up to 2000 m (total extension distance)
2
For power supply
H07 RN-F or 245IEC66
0.75 mm
2
, up to 50 m
3
For digital I/O
2-core cable
0.3 mm
2
, up to 100 m
■
About stripping length
Power supply wire stripping
length
Signal wire (TCC-LINK) stripping
length
Digital I/O cable stripping length
Attach a round crimp terminal to
each wire of the power supply wire.
About the shield grounding process
Shield of TCC-LINK communication line
When using a single Central remote
controller, open the shield of the TCC-
LINK communication line and perform
insulation processing.
When using multiple Central remote
controller, connect the shield of the
TCC-LINK communication line to the
closed end, open the shield at the final end
of the Central remote controller and
perform insulation processing.
Perform TCC-LINK communication line
shield grounding on the air conditioner
side.
About terminator resistor setting
TCC-LINK terminator resistor setting
Set on the air conditioner side. The
TCC-LINK terminator resistor is not set
in the Central remote controller. Leave
"open".
N
L
30
70
15
10
35
20
10
Round crimp
terminal
Power supply
wire