Central remote controller
Installation Manual
5
-EN
(1) Remove the 3 screws pointed to by arrows and open the cover
(2) Insert cross notches in the rubber bushing in order to pass the power supply cable
(3) Pass the power supply cable through the rubber bushing and the clamp, and connect the power supply wire and
the ground wire to the specified terminal block
(4) Close the power supply cover and secure with 3 screws
(1) Connect the TCC-LINK signal wire (U1/U2) to the terminal block
When connecting with an optional weekly timer, connect it to the WT connector.
Connect the power supply wire to the ground wire
Connect the signal wires
Cover fixing screw
Screws indicated by
arrows
Cover fixing screw
Power supply cover
Rear side
terminal block
Power terminal
Power supply wire
Clamp
Ground wire
Ground terminal
Rubber bushing
(Remove the transparent
cover at installation and
return it to its original
position after connecting)
(5)
(18)
WT
−
L N
COM
DI3
DI2
DI1
COM
DO2
DO1
U1
U2
Weekly
Timer
(sold separately)
TCC-LINK main bus
Outdoor unit
Indoor unit
Remote controller
Power supply: 220-240 VAC
Securely fix the cable with a
clamp.