Central remote controller
Installation Manual
6
-EN
(2) Connect to external equipment (digital I/O signal wire)
■
Connection to external equipment
* Wire the cables so that the user does not touch the power supply directly.
* On the equipment side, use a basically insulated power circuit and place it in a location where the user cannot touch it.
●
NOTE
• Do not connect the device directly to the primary side of the power supply.
Be sure to install a circuit breaker or all-pole isolating switch (with a contact breaking distance of at least 3 mm) on the
primary side of the power supply.
• Fasten the screws to the terminal with torque of 0.5 N•m.
—
COM
DI3
DI2
DI1
COM
DO2
DO1
U1
U2
Input common
Not used
All start input
All stop input
Control input
Output common
Operation
output
Alarm output
State output
Name
I/O Item
This unit side
Equipment side
I/O conditions
Circuit
Terminal name
Circuit example
I/O conditions
Digital
I/O terminal
State
output
Alarm output
Operation output
No-voltage contact A
Static
Contact permissible
voltage/current
24 VDC/35 mA
Control
input
All stop input
All start input
No-voltage contact A
Pulse or
static
No-voltage contact
compatible with very
small current must be
selected
5 VDC/3 mA
Pulse width:
300 ms or
more
Alarm
Run
Output common
Digital
Input
All start (+)
(Pulse or static)
5 V
All stop (+)
Input common (-)
COM
(Pulse or static)
5 V