TOSHIBA
3 - 3
3.0
Standard Specifications (Cont'd)
Display
4-digit, 7-segment LEDs
Output
Frequency range 0.0 to 400Hz and OFF state
frequency/
OFF
Warning
Stall preventive warning, overvoltage limit warning,
indications
overload warning, power-end undervoltage warning,
DC main circuit undervoltage warning, setting errors,
EEPROM abnormality, and data transfer abnormality
warnings
Fault
Overcurrent, overvoltage, load-end ground fault,
indications
overload, armature overcurrent at start-up, load-end
overcurrent at start-up, regenerative discharge
resistor overcurrent or overload, and fin overheat
Data and
Inverter status (forward/reverse run, frequency set
status
value, output current, etc.) and each set value
Speed
An arbitrary unit (revolution speed, linear velocity or
scaling
the like) as well as output frequency can bedisplayed
Data
A number is assigned to each inverter (for 0 to 31
storage
inverters).
LED
Charging
Main circuit capacitors charging indicator
indicator
Output signals
Fault detection signal
One form C contact (250AC / 30Vdc)
Low speed/reach signals
Open collector output (24Vdc, 50mA maximum)
Upper limit/lower limit
Open collector output (24Vdc, 50mA maximum)
frequency signals
Frequency meter output
Ammeter rated at 1mAdc at full scale, or voltmeter rated at
and ammeter output
7.5Vdc, 1mA
Enclosure type
Type 1 (standard), type 12 (option kits available)
*
Cooling method
Convection-cooled G2+2010 thru G2+2055 and G2+4015 thru
G2+4080
Fan-cooled G2+2080 thru G2+2330 and G2+4110 thru G2+430K
Color
Sherwin Williams Precision Tan #F63H12
Service
Service environment
Indoor, altitude 1000m (3,300 ft) maximum. Must not be exposed
conditions
to direct sunlight, or subjected to corrosive or explosive gas
or mists.
Ambient temperature
From -10 to 40°C (up to +50°C without the cover)
Relative humidity
90% maximum (no condensation allowed)
Vibration
Acceleration at 0.5G maximum (20 to 50Hz), amplitude at 0.1mm
maximum (50 to 100Hz)
ITEM
STANDARD SPECIFICATIONS
*
Enclosure for G2+430K has a removable bottom panel that must be drilled or punched in
the field to accomodate the wiring system conduit.
Summary of Contents for TOSVERT-130G2+