TOSHIBA
Terminal
Terminal functions
Terminal
name
location
ST
With ST-CC shorted, the inverter is ready to run. With ST-CC open,
a coasting stop phases in. This terminal can be used as a run
interlock.
F
With F-CC shorted, a forward run is engaged. With F-CC open,
deceleration phases in for a complete stop. (ST-CC is shorted.)
R
With R-CC shorted, a reverse run is engaged. With R-CC
open, deceleration phases in for a complete stop. (ST-CC is
shorted.) (If both F-CC and R-CC are shorted simultaneously,
a reverse run will result.)
CC
This is the common end of the PP, RR, and IV terminals.
Do not connect to GND(E).
SS1
With SS1-CC shorted, a multispeed run is engaged.
JOG(SS2)
With JOG-CC shorted, a jogging run is engaged: With SS2-CC
shorted, a multispeed run is effected. (See Section 8.4.3)
AD2(SS3)
With AD2-CC shorted, an ACC/DEC run is engaged; or with SS3-
CC shorted, a multispeed run will result. (See Section 8.4.4)
RST
With RST-CC shorted, the inverter's protective function resets.
CC
This is the common return for the ST, F, R, SS1, JOG(SS2),
AD2(SS3), and RST terminals.
Do not connect to GND(E).
OH
External fault signal input.
OV
Common connection for OH terminal.
GND(E)
The inverter earth ground terminal.
Do not connect to common return terminal (CC)
R41/46 *
Jumper to RJ when using 415V-50Hz/460V-60Hz incoming.
Do not jumper to R40/44 or R38.
R40/44 *
Jumper to RJ when using 400V-50Hz/440V-60Hz incoming.
Do not jumper to R41/46 or R38.
R38 *
Jumper to RJ when using 380V-50Hz incoming.
Do not jumper to R41/46 or R40/44.
RJ *
Common control voltage jumper terminal. Connects to R41/46 or
R40/44 or R38.
Do not jumper to more than one terminal.
4.10
Terminal Connections and Functions (Cont'd)
4 - 13
* Supplied only on the G2+4110 - G2+430K units.
Control
PWB
terminal
block
Frame
screw or
lug
Terminal
block
Terminal
block