TOSHIBA
7.2
Simple Operation (Cont'd)
Key
Action
Display
Assume the inverter is running at 55Hz.
Sets the inverter to 50Hz. The monitor will display "50" and "FC"
alternately. The inverter's frequency and motor's speed is decreased
to 50Hz, at the selected deceleration rate. Note the flashing semi-
colon ":". It signifies the motor is running but that the frequency
displayed is not necessarily the inverter's actual output frequency.
Displays the actual output frequency.
Press the key to raise the frequency to 60Hz. If the
WRT
key is
not pressed the 60Hz frequency will not be retained in memory should
the inverter lose power.
Displays the actual output frequency.
The inverter's output frequency will "ramp down" to 0Hz, causing the
motor to decelerate to a stop.
7 - 2
STOP
RUN
WRT
RUN
5
0
WRT
Note:
When an
invalid entry
is attempted, an error message and the "entered data" are
alternately displayed. For example, if a set frequency entered (FC) is higher than the
maximum frequency (FH) then the error message "FH" and the "entered data" are
alternately displayed. In this case, the set value entered will not be accepted and
therefore a correct set value must be entered.
Key
Action
Display
Assume the maximum frequency parameter (FH) is set to 80Hz, the
inverter is in the
monitor mode,
and the unit is not running.
Attempted to set inverter frequency to 90Hz (FC=90) but instead of
displaying
the unit will display
This signals a conflict between the value entered and the maximum
frequency FH.
The unit will accept this value since there is no conflict between the
value entered and FH.
9
0
WRT
8
0
WRT